REFCO DIGIMON User Manual

Digimon instruction manual, Digimon, For the 2-way digital manifold

Advertising
background image

7

3 1

6

4

2

5

1

HVAC/R

Service Products

REFCO Manufacturing Ltd.

Telefon +41 41 919 72 82

Industriestrasse 11

Telefax +41 41 919 72 83

CH-6285 Hitzkirch (Switzerland)

[email protected] www.refco.ch

DIGIMON Instruction manual

for the 2-way digital manifold

DIGIMON

Important

Read this manual carefully and familiarise yourself with the specifi-

cations and operation of the REFCO DIGIMON digital manifold prior

to use. These instructions provide important information regarding to

the operation and service of the manifold.

Purpose and use

The manifold has been designed specifically to measure pressure and tem-

perature in refrigeration equipment. For use only by trained technicians.

The manifold must not be used for other than refrigerant applications.

The manifold is not suitable for other liquids or gases except those

indicated on the display.

The manifold must not be used with pressure higher than 870psi /

60bar / 6000kPa / 6MPa.

The manifold cannot be used as a pressure regulator, especially not in

use with nitrogen N

2

.

The manifold cannot be used with ammonia (NH

3

/ R717).

Do not expose the manifold to rain or wet conditions.

1) Low pressure anchor ¼“ SAE

2) High pressure anchor ¼“ SAE

3) Low pressure valve (blue)

4) High pressure valve (red)

5) Vacuum + refrigerants anchor ¼“ SAE

6) External K-type thermocouple

7) Clamp thermocouple K- type, P/N 4681466 (optional)