OPERATION

IMPORTANT: When the Sanuvox SR+ is turned on by pressing the POWER button, the RED LED on the POWER button will

illuminate and the status LED will flash in alternate colors singling the SR+ is warming-up. The warm-up will last approximately 45

seconds, after which time the unit will enter ‘STANDBY-MODE’. THE UNIT WILL NOT FUNCTION UNTIL THE WARM-UP IS

COMPLETE.

1.

Once the SR+ is in ‘STAND-BY’ mode, the unit will be waiting for airflow in order for the UV Lamp to turn ON. The SR+ has a built-in

Thermistor that controls operation. When there is airflow the Thermistor changes temperature causing the SR+ Lamp to come on. When

airflow stops, the SR+ UV Lamp will turn OFF accordingly.

2.

When in ‘STAND-BY’ and there is airflow, the SR+ UV Lamp will come ON and the LED will illuminate GREEN.

3.

When there is no airflow, the status LED will be OFF and the RED POWER Button LED will remain ON.

SR+

INSTALLATION

MANUAL

PLEASE SAVE FOR YOUR RECORDS

Serial Number#

Date Installed:

Installed By:

Installers Contact info.:

SANUVOX TECHNOLOGIES INC. © 2013

Follow all safety codes.

Wear safety glasses and work gloves.

1-888-SANUVOX www.sanuvox.com

Before installing or performing maintenance or

service on the purifier, turn off unit and disconnect

from power source. Electrical shock can cause

injury or death. There may be more than one

disconnect switch.

Never expose eyes or skin to ultraviolet light from

any source. The Purifier MUST be DISCONNECTED
from power source before performing maintenance

or service. Personal injury may result.

Do not touch Lamp glass without gloves. Reduced

performance of Lamp may result. Clean Lamp after

handling.

Use only specified replacement Lamps with you

Purifier. Use of an incorrect Lamp can result in

damage to the Purifier and/or Lamp.

WARNING

WARNING

WARNING

The UV Lamp contains a small quantity of mercury.

If a Lamp breaks, clean and dispose of with care.

WARNING

WARNING

UNDERSTANDING THE LED STATUS DISPLAY

Troubleshooting the UV Lamp
To check to make sure the UV Lamp has in fact failed:

UV LAMP RESET BUTTON (To be used to reset “Days Left” after UV Lamp change-out)

Disconnect the plug from the Lamp.

Placing the probe of the ohmmeter to one of the four pins on the end of the Lamp, touch the other probe of the ohmmeter to each of the other pins
until you find the matching pin. The ohmmeter shows continuity (closed circuit). This indicates that the filament is good. Check the other two pins. If
both sets of filaments test OK (continuity), the Lamp is functioning. If one or both sets of filaments read an open circuit (no continuity) on resistance,
the Lamp must be replaced.

To the bottom right of the SR+ cover right you will see a small REST hole. To RESET the UV Lamp Replacement LED Reminder back to 3 years,
insert a small object similar to a paper clip into the hole holding down the button for 3 seconds.

04/13 V.4

1-888-SANUVOX www.sanuvox.com

LED Solid GREEN = SR+ is ON with UV Lamp ON sensing airflow

LED Flashing GREEN = Warm up sequence lasting up to 45 seconds

LED Flashing ORANGE = UV Lamp has functioned for 3 years and is due for replacement.

LED Solid RED = UV Lamp has FAILED. Must be replaced

LED Alternating RED+GREEN = Thermistor Issue

LED OFF = Unit is on Stand-by (provided RED power button LED is illuminated)

NOTE: The only time the RED Power button LED will be OFF is if power is interrupted to the
unit or the Power Button is in the OFF position.