Sanuvox UV BIO-WALL QUATTRO User Manual

Quattro installation manual, Warning, Questions? call 1-888-sanuvox

Advertising
background image

QUATTRO

INSTALLATION

MANUAL

Before installing or performing maintenance or service
on the purifier, turn off main power switch to unit.
Electrical shock can cause injury or death. There may
be more than one disconnect switch.

Never expose eyes or skin to ultraviolet light from any
source. The Purifier MUST be DISCONNECTED from
power source before performing maintenance or service.
Personal injury may result.

Do not touch Lamp glass without gloves. Reduced
performance of Lamp may result. Clean Lamp after
handling.

Use only specified replacement Lamps with your
Purifier. Use of an incorrect Lamp can result in damage
to the Purifier and/or Lamp.

WARNING

WARNING

WARNING

The UV Lamp contains a small quantity of mercury. If a
Lamp breaks, clean and dispose of with care.

WARNING

PLEASE SAVE FOR YOUR RECORDS

Serial Number#

Date Installed:

Installed By:

Installers Contact info.:

WARNING

SANUVOX TECHNOLOGIES INC. © 2009

Follow all safety codes.

Wear safety glasses and work gloves.

QUATTRO

INSTALLATION

MANUAL

Questions? Call 1-888-SANUVOX

1-888-SANUVOX www.sanuvox.com

Trouble-Shooting the UV Lamp

RETURN OR SUPPLY PLENUM INSTALLATION

OPERATION

The QUATTRO has an ON-OFF toggle switch and a circuit breaker located at the bottom of the front cover. To operate, press
the toggle switch to the “ON” position. The switch has a red light to indicate that there is power. If the switch does not illuminate,
check the outlet for power and check the QUATTRO circuir breaker. Start the HVAC fan. The QUATTRO detects airflow with the
vacuum switch. The QUATTRO will only operate when the fan is ON (airflow through the plenum) and there is a pressure
differential of at least 0.04 in.

When operating, the LED lights on the front cover will be lit. There are two LED lights corresponding to each of the 4 UV
Lamps. The BLUE LED indicates the UV Lamp is functioning. The GREEN LED indicates the Ballast is ON. If the UV Lamp is
defective, the GREEN LED will be lit corresponding to the BALLAST being ON and BLUE LED will be OFF corresponding to
Lamp out. If both LED lights are OFF, the ballast is not functioning. If none of the 8 LED lights are lit, then there is not enough of
a vacuum differential to activate the vacuum switch, or the vacuum switch is defective.

Fiberglass or paper filter media are recommended for operation of HVAC when filters are exposed to direct line of sight with the
ultraviolet light. Polyester or cotton filters are subject to ultraviolet degradation and are nor recommended.

MAINTENANCE

Disconnect all power before performing any maintenance or service. Lamps need periodic replacement to maintain design
specifications. In residential applications, replace UV after 3 years of operation. In commercial applications, replace Lamps after
2 years of operation.

The following UV Lamps are used with the following QUATTRO models:

QUATTRO G : 4 x LMPHGS180 UV Germicidal only
QUATTRO GX : 3 x LMPHGS180 UV Germicidal only + 1 x LMPHGXS180 UV Germicidal / Oxidizing

Checking the UV Lamp

Sanuvox Ultraviolet Lamps are built to the highest standards. If the
Green LED (Ballast) is lit and the Blue LED (Lamp) is not lit, it is
important to check the Lamp to insure that it is not a defect in the Lamp
Sensing Circuit in the Ballast. This is done by using an ohmmeter to
check the two filaments on the Lamp.

Disconnect the socket from the Lamp.

Placing the probe of the ohmmeter to one of the four pins on the end of
the Lamp, touch the other probe of the ohmmeter to each of the other
pins until you find the matching pin. The ohmmeter will read
approximately 3 ohms (almost a short). This indicates that the filament
is good. Check the other two pins. If both sets of filaments test OK, the
Lamp is functioning. If one or both sets of filaments read an open circuit
(infinity) on resistance, the Lamp is defective.

1.

Cut a 6¼” W x 23½ ”H opening in the duct-work at the desired installation location.

2.

OPTIONAL: Install the added reflectivity if desired.

3.

Adjust the UV Lamp assembly so they will be positioned in the middle of the duct. The arms that support the
Lamp assembly have an adjustable clutch which allows the Lamps and extrusion to be set at a distance from 10
to 15 inches from the backplate. To adjust the assembly, loosen the clutch by turning it counter-clockwise (see
Figure B.). The Lamps and extrusion can then be positioned to the desired distance from the backplate. Rotate
the clutch clockwise to tighten.

4.

Place the QUATTRO in the duct opening in the correct orientation. Mount to duct-work with 12 self taping
screws provided.

5.

Plug in the power cord.

Advertising
Table of contents