CIRCUTOR WRU-RAL Series User Manual

CIRCUTOR Measuring instruments

Advertising
background image

GENERAL DESCRIPTION

Código
code

Tipo
Type

Sensibilidad (A)
Sensivity

Retardo disparo (s)
Tripping delay

P24457 WRU-10 RAL 0.3-1

0,3-0,5-1 por ajuste directo/by direct setting

INS 0,02 por ajuste directo / by direct setting

WRU-10 RAL 0.3-1 Electronic Earth-leakage Protection Relay

Peso / Wheight : 168

REC

RAL

REC

R

REC

- DELAY SETTING

- SETUP ROTATION

- ENABLE/DISABLE
SELF-RECLOSING SYSTEM

- SENSIVITY SETTING

- outputs contacts SETTING.
(LOCKED SIGNAL)

REC

REC

REC

R

.

DESCRIPTION LED AND BUTTONS

Shows equipment status via a
display and 2 LED's. It has 5
button equipment setup and
setting and 2 button equipment to
do TEST and RESET.

- SETUP settings

- change PAGES

- GREEN led

: ON

- RED led, tripped by fault.
- blinking led: pre-alarm

- Reclosures led:
fix, maximun reclosures
blinking, betwen reclosures

- RESET Button

- TEST Button

+

REC

PROG

Super-inmunized Type A electronic relay. Built-in core balance
transformer, 28 mm.Device with self-reclosing system. Symbol on
display. It has programmables relays, 3 outputs. Main trip and 2 pre-alarm signals. It has 1
free voltage input for external ON / OFF. Mounting in DIN rail 46277 (En50022) or PANEL
72x72 by means of accesories M5ZFF1. Displays setting values and instantaneous earth
leakage current value (TRMS)

PRELIMINARY CONSIDERATIONS

CHECKS ON RECEPTION
On receving the instrument, check the following points:
- The unit’s specifications are the same as those on your order.
- Check that the device has not suffered any damage during transport.

You can download more information from CIRCUTOR website, www.circutor.es

SAFETY PRECAUTIONS
The staff using or handling the unit must follow the common safety measures and warnings included in the
instruction manual.

The WRU-10 unit has been specifically designed for its installation in a electric board, enclosure to a DIN
rail or mounted in panel by means of accesories. It has a flashing green led (ON) when it is operation and,
therefore, it shows that there is voltage and current in the electronic circuit. The user must make sure that
the equipment is not conected to the power supply at all the times, even when the LED is not flashing.

The user must take into account and observe the informations and warnings included in this instruction
manual to guarantee the correct operation of the equipment and comply whit the safety specifications. The
equipment must not turned on until is fully installed in the electrical panel.

Disconnect the equipment from the power supply when the unit´ssafety protection systems are not working
or there are signs of a problem (in case of visible damage). In this case, contact a qualified technical service
or with our own technical service (TAS).

INSTALLING THE EQUIPMENT

DIN rail installation. On the inside of the hole must pass all live conductors supplyng electrical energy to
loads or part of the installation which requires it to earth leakage protection with this device. In single-phase
installation (phase and neutral, L and N), three phase - 3 wires (three phases, L1, L2 and L3) or three
phases - 4 wires (L1, L2, L3 and N). Depending on the level of wiring insulation can be pass through the hole

2

2

of 28 mm (inner diameter) 4-wire 35 mm of section, although it advisable is 25 mm . All connections

INSTALLATION AND STAR-UP

¡ IMPORTANT !

!

The unit´s protections systems might not be effective if the unit is used for purpose other than
those specifications by the manufacturer.

should be inside the electrical board. Please note that with the connected equipment, terminals and
opening covers or removing elements, can give access to dangerous parts to touch. The equipment must
not be used until it has completely finished installation. The unit must be connected to a power supply circuit
protected by fuses in line with the range and power consumption. In turn, the supply circuit must be
provided with a circuit breaker or equivalent device to disconnect the equipment from the mains. During the
wiring cable is advisable a section permitted between 1 - 1.5 mm2. A recommended torque of 0.5-0.6 N.M.
Cable Stripping Tools length 7 mm.

Power supply Operating conditions Safety

Category III - 300 Vac (En61010)
Double - insulated electric shock protection
clas II - UL 1053 UL Certification -
IEC 60755 - IEC 60947-2 Annex M

Voltage 230 Va.c..
Frequency 50!60 Hz
Burden 4,5 VA

+/- 30% Temperature -20...70 C

Relative humidity 95%
Max. Altitude 2.000 m
Protection Ip20

CONNECTIONS BY MEANS OF PLUG-IN CONNECTORS

Rated current: 5 Ac.a.
Rated voltage: 250 Vc.a.
Rated Load: 1.250 V·A

Rated current: 0,25 Ac.a.
Rated voltage: 230 Vc.a.
Rated Load: 62,5 V·A

Free voltage, not isolated

Protected by varistor:
420 Vc.a. - 10 Ac.a.

TERMINAL DESCRIPCIÓN FEATURES

1 - 2 EXTERNAL INPUT TRIP / RECLOSE
3 PRE-ALARM OUTPUT RELAY, NO
4 PRE-ALARM OUTPUT RELAY COMMON
5 LOCKED OUTPUT RELAY, NC
6 LOCKED OUTPUT RELAY COMMON
7 SUPPLY 230 Va.c. (Phase or Neutral)
8 SUPPLY 230 Va.c. (Neutral or Phase)
9 TRIPPING OUTPUT RELAY, NC
10 TRIPPING OUTPUT RELAY, NA
11 TRIPPING OUTPUT RELAY COMMON
12 WITHOUT USE

Technical Assistance Service (T.A.S)

If you have any doubts about the running of the equipment or any faults, contact the service staff.

Tel: (+34) 93 745 29 19
Fax: (+34) 93 745 29 14
email: [email protected]

Vial Sant Jordi s/n
08232 Viladecavalls (Bacelona) SPAIN

RAL

Tripping cause

Mensage display

Test

Remote signal trip/reclose
Earth leakage fault

TESt
EXT

alue

DIF / v

SAVE
EXIT
OVR

Enter setting values
Exits setting mode
Value reading off scale

Other mesages by display

-

.

.

-

-

-

-

- BY
1.

.

2. Manual reclose by pushing button RESET.
3.

(

t , I and std/+ )

d

d

-

, t .

d

t

d

.

SAVE.

-

, I .

I .

d

d

- SIGNALLING CONTACTS RELAY STATE, std/+ . Select the default position of the relay contacts
4-5-6 that indicates the situation of locked by reclosures of the device . In (Std) 4-6 NO / 4-5 NC
and (+) 4-5 NC / 4-6 NO and appears the symbol in display

.

- SELF-RECLOSING SYSTEM, REC. In reclosure partial numbers by press REC button we
configure the self-reclosing sequence referred at the page which it’s showing us. By default is
configured nº12 by earth leakage protection.

INDICATION BY LED AND DISPLAY

MAIN TRIP RELAY LED and display signals a

change of status by changing from green to red.
Display event type messages or values

PREALARM SIGNAL. The LED green is blinking

betwen green and red.

BETWEN RECLOSURES. LED is blinking
LOCKED BY RECLOSURES. The yellow LED is

fixed. The equipment arrives al maximun number of reclosures established by the self-reclosing
sequence. Red display shows the cause.

No OF RECLOSURES. By short press on the display shows the number of reclosures by earth

leakage faults, partial and total number. The partial number are floating pages. In these pages
it can configure the self-reclosing sequence by press button.

RECLOSING THE EQUIPMENT.

TRIP LOCKED BY RECLOSURES

Automatic (earth leakage fault or manual). Is shown on display

External reclose sytem by remote or communications signal. When it forces a trip by remote
signal, only it can reclose by another remote signal. In the case 2 and 3 the partial counters

of reclosures returns to a zero.

MAIN RELAY PARAMETER SETTING

SETTING TRIP DELAY

The message and two values appear on the screen after

pressing the

button. The lowest value indicates the current set value and the highest is the

values to be configured which are displayed by pressing

The selected value to be saved is

displayed by showing the message

SENSITIVITY SETTING

The same operation as above setting is carried out by pressing

¡ IMPORTANT !

The relay only self-recloses after a trip by earth leakage current fault. The Test (red button) only verifies the relay trips
the protection. It recloses only by manual pressing RESET button.

0
1 6 8, 16, 30, 59, 115 y 224 s 15 minutes
2 30 20, 40 s y 5 min. to the end. 15 minutes
3 8 30 s, 1, 2, 3, 4, 5, 6 y 7 min 15 minutes
4 6 10, 20, 30, 60, 130 y 600 s 15 minutes
5 6 2, 4 y 8 min. to the end. 15 minutes
6 7 30 s, 1, 2, 3, 4, 8 y 16 min 30 minutes
7 10 1 min 30 minutes
8 10 90 s 30 minutes
9 8 2, 4 y 6 min. To the end. 15 minutes
10 10 3 min 30 minutes
11 7 2, 4, 8, 16, 32, 32 y 32 min 15 minutes

DISABLED

12 31 2, 4 y 6 min. to the end. 60 minutes
13 3 2, 4 y 8 min 15 minutes
14 ... ... ...

SREC No RECLOSURES TIME SEQUENCES RESET TIME

PROG

With the

button the submenus are browsed

and with the button the values to be selected
are displayed

to enter the value. The equipment

configures the value by displaying

on the

display and then exits Setting Mode If the keypad
remains inactive for a certain time, the equipment
automatically exits Setting Mode and displays

.


Press

SAVE

.

PROG

PROG

SETUP SETTINGS

FREC

LIM

ALAR

RSTC

Button

PROG

50 Hz
60 Hz

10 s, 30 A

I

d

t

d

SP

Pre-alarm current %

Delay pre-alarma seg.

Contact NO/NC

AU Reconectable

1 s, 3 A

OFF
50
60
70
80
MAIN
0,02
0,1
0,2
0,3
0,4
0,75
1
3
NO
YES
AUTO
MANU
NO
YES

Button

- FREQ,

(50) frecuency (Hz)

- LIM,(1s, 3A), range of values (Id / td)
- ALAR, pre-alarm.
. Id (MAIN),100%.
. Td ( 20 ms), time.
. SP (NO),contact states.
3-4 [NA/NC]
.AU (AutO), Relay reclaim the state.
- RSTC, (NO), Reset the partial reclosures.

Default values in SETUP

M008A01-03-14B