Default plug&play values, Manual, Etup – CIRCUTOR computer PLUS-TF Series User Manual

Page 36

Advertising
background image

36

If there is an error message at the end of the automatic adjustment process, carry out the process again
and if the error persists, the system must be adjusted manually, as described in section 7.3.

If the error message is not displayed at the end of the automatic setting, press the Run key to assess
whether the cosine values of fi and the value of kvarC connected are logical or not (see Fig. 41). If they
are correct, press the Run key again and the regulator will start to operate.


7.2.5

Default Plug&Play Values

Some parameters affect the compensation process and they are configured by the Plug & Play by default.

The default values of the parameters are shown on table 7.1.

Parameter

Meaning

Default values

cos

objective

Desired cos value

1

Default connection of

capacitors

Steps configuration

Delta

Tact

Connection/Disconnection time between

steps

10 s

Trec

Reclosing time of the same step

50 s

V1/V2 voltage transformer

ratio

Transformer ratio of voltage measurement

transformers (generally 1, except in the

case of MV or HV)

1/1

Current transformer

secondary

Nominal value of I2

/5

Menu language

Spanish

Parameters of the

communications channel

Parameters of the communications

channel

Peripheral...1

Baud rate… 19200

Parity... No

Leng. Data… 8 bits

Bits Stop… 1

Table 7.1.- Parameters configured by default

7.3

MANUAL Setup

Even though the easiest way of configuring Computer plus is with the Plug & Play option, all of the unit's
parameters can also be configured manually.