Adjusting the transformer ratios – CIRCUTOR computer PLUS-TF Series User Manual

Page 40

Advertising
background image

40

To edit the information on the screen shown on Fig.47, press the

Edit option and the screen shown on

Fig.48 will be displayed. Use the arrow to change the field being edited. Pressing

Edit again we may

change IB by IC, for example, or S1-S2 by S2-S1.

If you do not know how the cables of the current transformers (CTs) are connected, try various
combinations until you obtain a coherent cos

reading. Imagine this can be achieved with the setup

shown on Fig. 49. This would mean that the CT of phases 2 and 3 are changed and that the secondary
of phase 3 has S1-S2 inverted.

Fig. 48.- Menu to change CT connections

Fig. 49.- Menu to change CT connections

When the setup is producing a coherent set of cos

values, press

OK and adjust the transformer

connections.


7.3.6

Adjusting the transformer ratios

In this menu, the voltage transformer and the current transformer ratios can be adjusted. In general, there
will only be voltage transformers in the medium or high voltage systems (MV or HV). In the case of low
voltage installations, the voltage transformer ratio is 1:1.

To adjust the transformer ratios, proceed as follows:

Open the setup menu by following the process described in section 7.3.2

From the list of options, select Transf. Ratio (screen on Fig.50) and press

OK to display the screen

shown on Fig.51