CIRCUTOR DISPENSER Series User Manual

Page 42

Advertising
background image

Figure 44: Screen used to create a new micro-grid�

Fill in the following fields to create a new micro-grid,

Table 6

:

Table 6:New micro-grid: Micro-grid information�

Parameter

Description

Name

Name of the micro-grid

Micro-grid identifier

Select the ID no. of the micro-grid

(Drop-down list, from 1 to 100)

Operator

(1)

Name of the operator

Phone

Contact number of the operator

Geographical coordinates:

(1)

Latitude and Longitude

Latitude and longitude of the micro-grid

(1)

These fields are not mandatory.

If you want the micro-grid to operate in the

Frequency mode, enter the frequency values for

each state of the micro-grid,

Table 7

.

Table 7: New micro-grid: Frequency mode�

Parameter

Description

Default value

(2)

Type of micro-grid

Select the type of generators used in the mi-

cro-grid:

Solar power with batteries, Diesel

generator or Other.

Solar power with batteries

Frequency

Working frequency of the micro-grid

50 Hz

Hysteresis between

mode changes

Time between the change of states, in seconds

300 s.

Excess

Input frequency of the excess factor

52.5 Hz

Limitation

Input frequency of the limiting factor.

48.5 Hz

Bonus

Input frequency of the bonus factor

52 Hz

Restriction

Input frequency of the restriction factor

49 Hz

Auxiliary relay activa-

tion

Frequency required to activate the auxiliary relay.

52 Hz

(2)

Default values for a solar power micro-grid with 50Hz batteries.

42

Dispenser Universal System

Instruction Manual