Crompton Controls 3DS1- -I User Manual

Starters, Installation and maintenance instruction for

Advertising
background image

That the starter is suitable for the operating

environment.

General inspection of the starter should be carried out

to make sure that there has been no damage caused
by transportation or storage.

M o d e r n h i g h -

performance contactors rely on the low inertia of their
moving parts to achieve this performance. Because of this,
any knocks or vibration can seriously affect the
performance of these starters. It is essential, therefore, that
the starter should be mounted away from any vibration
and in a position where it is extremely unlikely that the
starter will receive any knocks.

Although the starters are protected to IP55 thereby
restricting the ingress of dust and moisture, the starter
should be mounted in such a manner as to minimise the
effects of dust and moisture. In particular, the effects of
condensation occurring within the starter should be
minimised.

It is essential, where dust and moisture are present, to take
particular care when fixing the starter to the mounting
surface and when making conduit connections to ensure
that these areas are properly sealed.

When the mounting position has been decided, it may be
advantageous to remove the starter interior from the
enclosure to remove the knockouts, fasten the base to the
mounting area and to complete the external wiring.

Where the only connection to the cover is an earth
connection, this should be disconnected. Do not allow the
cover to hang on the earth lead as this may affect earth
continuity.

The starters are fitted with single

knockouts and the methods of removal are shown below:-

All wiring connected to the starter should be in

accordance with the latest edition of The Institute of
Electrical Engineers Regulations for Electrical Installation.

It is essential that earthing of the starter is carried out in a
proper manner. This is preferably done by the use of a
separate earth conductor which also connects through to
the motor. We do not recommend earthing via mounting
points or conduit fittings, as these can become corroded
and affect earth continuity.

The starter, cabling and the

motor should be protected against short circuit conditions
by adequately rated fuses or circuit breakers.

The overload unit fitted to the starter should be set to
correspond to the full load current of the motor,

Some starters may be fitted with Thermistor

Protection units used in conjuction with thermistors fitted
in the motor to give over-temperature protection. The
protection given in this case is dependent on the
thermistors fitted to the motor and consequently
adjustment of this unit is not required.

Before applying

power to the starter, it is advisable to carry out the
following checks:-
Check all mechanical fixings to ensure that they are
tight.

L O C AT I O N A N D M O U N T I N G

KNOCKOUTS

WIRING

CIRCUIT PROTECTION

NOTE: -

FINAL CHECKING AND TESTING

.

This leaflet carries important information in respect of
Health and Safety at Work and should remain with the
starter at all times. Extra copies, if required, are available
from the address shown.

Crompton Controls 'Series 3000' starters are
manufactured to British standards BSEN60947-Pt4-Sec 1.
BSEN60529-1992 and to IEC947-4-1. Crompton Controls
manufacture the starters under a Quality Management
System registered to ISO 9001:2008. All starters give degree
of protection IP 55 (minimum) and are suitable for use up
to an altitude of 2000 meters above sea level and for
operation in ambient temperatures of -5° C to +40° C

All electrical equipment for operating on low voltages
contain devices which are capable of causing serious
or fatal injuries.

Any person who is involved on installation or
maintenance of this equipment should be fully
competent to carry out this work. Such persons should
be familiar with the Health and Safety at Work Act 1974
and the Electricity at Work Regulations 1989. Persons
responsible for installation should also have a working
knowledge of the IEE Wiring Regulations.

The following points should be checked

before commencing the installation of the starter.
That the equipment is suitable for the voltage of the
system.
That the setting range of the overload unit is suitable

for the motor involved.

PREPARATION

.

INSTALLATION AND

MAINTENANCE INSTRUCTION

FOR

STARTERS

IMPORTANT

GENERAL

INSTALLATION

1

SAFETY

IMPORTANT

KNOCKOUTS: WHEN REMOVING KNOCKOUTS
CARE MUST BE TAKEN NOT TO DISTORT THE SIDE OF
THE ENCLOSURE.

Single knockouts are designed to be removed INWARDS
with a twisting/rocking action by applying a small chisel or
similar tool to the extreme edge of the knoclout at 90 to
the retaining lugs and tapping with a hammer. Move tool
across to the other edge and repeat process until knockout
is released.

o

Check all terminals to ensure that they are tight

especially the earth connection.

Check that the moving contact carriage of all contactors
are free to operate.
Set any timers which may be included in the starter to
the approximate time required.
Ensure that the earth connection between base and
cover is in place.

In the interest of safety, we recommend that the
cover of the starter is secured in place before
applying power to the starter and that testing
should only be carried out in this condition. Any
adjustments which may be necessary should be
c a r r i e d o u t w i t h t h e s u p p l y i s o l a t e d .

As a general rule, this equipment should be
disconnected from the supply before carrying out
work of any nature. However, there may be times,
particularly during servicing when it is necessary to
work on the equipment with the supply connected
(e.g. checking

Although these starters have been designed to afford
finger protection, it is essential to observe the following
precautions before working on the starters with the
supply connected:-
Ensure that it is absolutely necessary to work on the

equipment whilst in a live condition.
Ensure that you are fully aware of the layout of the
starter and where to expect live connections.
Ensure that you are within sight of other people who
could come to your aid if necessary.
Ensure that any tools or equipment used are suitable
for working on live equipment.

Should you have any

doubts regarding operational problems, application of
starters or any technical queries, our technical staff are
available to advise. This advice is available via our field
Sales Engineers or via our Head Office as shown on this
leaflet.

In the unlikely event of faulty

operation, please check the complete system. If you are
certain that the fault lies in the starter, contact your
supplier who will negotiate any warranty claim with
Crompton Controls. In the event of any difficulties, you
may contact Crompton Controls direct at the address
shown on this leaflet.

Crompton Controls 'Series 3000' starters are

designed to give long trouble-free operation. The life of
the starter will, of course, depend on the duty to which it is
subjected. The operational (electrical) life at full current
rating of the contactors is designed to be 500,000
operations .
However, as with any equipment, it is advisable to carry out
routine checks to ensure that there are no problems
developing which could cause failure.

Before carrying out routine checks, it is

important to observe safety precautions printed in bold
type under installation.
The following checks are advisable:-
Check all screws, fixings and terminals to ensure that
they are tight.
Check all moving parts for ease of operation.
Examine all wiring for damaged insulation.

Check cover seals and conduit entries to ensure that
sealing is still intact.
Check all earth connections.
Check visually for signs of overheating or arc damage.
Any such damage should be investigated and
remedied without delay.

Check for ingress of dust and/or moisture which could

adversely affect the equipment.

When fitting an overload relay into this starter the

following procedure should be observed.

voltages and currents).

.

.

.

.

.

.

OPERATIONAL PROBLEMS

FAULTY OPERATION

GENERAL

CHECKING

1

2

3

4

3

6

4

7

5

a

b

c

d

e

8

a

b

c

d

MAINTENANCE

1

2

2

3

2

1

WORKING ON LIVE EQUIPMENT

4

5

7

6

OVERLOAD RELAY FITTING INSTRUCTIONS

Advertising
Table of contents