Contemporary Control Systems Modbus Cube I/O MR-AO4 User Manual

Analog output module mr-ao4

Advertising
background image

2. Declaration of Conformity

The device was tested according to the applicable standards.

Conformity was proofed. The declaration of conformity is

available at the manufacturer BTR NETCOM GmbH.

Notes Regarding Device Description

These instructions include indications for use and mounting of

the device. In case of questions that cannot be answered with

these instructions please consult supplier or manufacturer.
The indicated installation directions or rules are applicable to

the Federal Republic of Germany. If the device is used in other

countries it applies to the equipment installer or the user to

meet the national directions.

Safety Instructions

Keep the applicable directions for industrial safety and preventi-

on of accidents as well as the VDE rules.
Technicians and/or installers are informed that they have to

electrically discharge themselves as prescribed before installati-

on or maintenance of the devices.
Only qualified personnel shall do mounting and installation

work with the devices, see section “qualified personnel”.
The information of these instructions have to be read and un-

derstood by every person using this device.

Symbols

Warning of dangerous electrical voltage

Danger

means that non-observance may cause risk of life,

grievous bodily harm or heavy material damage.

Qualified Personnel

Qualified personnel in the sense of these instructions are persons

who are well versed in the use and installation of such devices

and whose professional qualification meets the requirements of

their work.
This includes for example:

• Qualification to connect the device according to the VDE

specifications and the local regulations and a qualification to

put this device into operation, to power it down or to activate

it by respecting the internal directions.

• Knowledge of safety rules.

• Knowledge about application and use of the device within the

equipment system etc.

1. Description

The Modbus module with 4 analog outputs is designed for local

switching operations. It is suitable as variable encoder, for ex-

ample ventilation or mixing valves, valve positions etc. The out-

puts can be adjusted via a Modbus-Master. Setting of the slave

address, bit rate and parity is done with the two address

switches (x1 / x10) on the front. Possible settings are addresses 00

to 99 and bit rates 1200, 2400, 4800, 9600, 19200, 38400, 57600

und 115200 Bd.
The device does not participate in bus communication if the

address is 00 (reserved for broadcast commands).
Communication with the master can be monitored with a

watchdog timer. If master or communication fail the outputs are

switched to their basic state (secure state) and the red LED is ligh-

ting. The timer restarts with each valid message addressed to the

device. When defining the time constant it is necessary to take

account of the baud rate, the number of slaves on the bus and the

length of the messages per slave.

7162/899293

Analog Output Module

MR-AO4

1108351302

5. Connection Diagram

C2

4

C2

3

1

C2

2

C2

24 V AC/DC

GND

BUS A-

BUS B+

A2

A-

B+

A1

A2

A-

A1

B+

4. Wiring Diagram

A2 = C2 = GND

3. Technical Data

Modbus Interface

Protocoll

Modbus RTU

Transmission rate

1200 ... 115200 Bd

(factory setting 19200 Bd Even)

Cabling

RS485 two wire bus with voltage

equalizing cable in bus / line topology

Supply

Operating voltage range 20 ... 28 V AC/DC (SELV)
Current consumption

50 mA (AC) / 20 mA (DC)

Relative duty cycle

100 %

Output

Output voltage

4 x 0 ... 10 V DC

Output current

5 mA at 10 V DC

Resolution

0.625 mV / Digit

Error

100 mV

Housing

Dimensions WxHxD

1.4 x 2.8 x 2.6 in. (35 x 70 x 65 mm)

Weight

72 g

Mounting position

any

Mounting

standard rail TH35 per IEC 60715

Mounting in series

the maximum quantity of modules

without space

connected in line is limited to 15 or to

a maximum power consumption of

2 Amps (AC or DC) per connection to

the power supply. For any similar

block of additional modules a

separate connection to the power

supply is mandatory.

Continuation Technical Data

Material

Housing

Polyamide 6.6 V0

Terminal blocks

Polyamide 6.6 V0

Cover plate

Polycarbonate

Type of protection

(IEC 60529)

Housing

IP40

Terminal blocks

IP20

Terminal blocks

Supply and bus

4 pole terminal block

max. AWG 16 (1,5 mm²) solid wire

max. AWG 18 (1,0 mm²) stranded wire

Wire diameter

min. 0.3 mm up to max. 1.4 mm

(terminal block and jumper plug are

included to each packing unit)

Module connection

Input/Output

max. AWG 12 (4.0 mm²) solid wire

max. AWG 14 (2.5 mm²) stranded wire

Wire diameter

min. 0.3 mm up to max 2.7 mm

Temperature range

Operation

-5 °C ... +55 °C

Storage

-20 °C ... +70 °C

Protective circuitry

polarity reversal protection of

operating voltage

polarity reversal protection of supply

and bus

Display

Operating and bus activity green LED
Error indication

red LED

METZ CONNECT | Im Tal 2 | 78176 Blumberg | Germany | Phone +49 7702 533-0 | Fax +49 7702 533-433
Distributed by RIA CONNECT GmbH and BTR NETCOM GmbH
Mounting instruction see www.metz-connect.com

Advertising