Crydom DRA Series Contactors User Manual

Installation sheet, Dra series contactors, Din rail mount

Advertising
background image

Rev: 112213

3 Phase AC Contactors &

AC Motor Reversing Contactors

FEATURES

45 mm wide 3 phase & 62 mm wide motor reversing DIN rail mountable versions available

480 VAC Operating Voltage

5 VDC, 24 VDC, 48 VAC, 120 VAC & 230 VAC Input Control Voltage options available

Protective Forward/Reverse interlock built-in function for motor reversing

UL and IEC general use & Motor ratings available

LED Status indicator for Input Control Voltage

INSTALLATION INSTRUCTIONS

Please read all installation instructions before using DRA Series 3 Phase / Reversing Contactors.

fig. 1

Mounting/Dismounting contactor on DIN rail.

To install on DIN rail

To remove from

DIN rail

PART NUMBER NOMENCLATURE

DERATING CURVE

Required for valid part number
For options only and not required for valid part number

Lo

ad

C

ur

re

nt

(A

m

ps

)

0.0

1.0

2.0

3.0

4.0

5.0

0

10

20

30

40

50

60

Ambient Temperature (°C)

DRA3xxxx2

DRA3xxxx4

DRA Series Solid State Contactors offer the advantages of Crydom's proven state-of-the-art solid state AC

switching technology in a ready-to-use contactor which requires no additional heat sinking. DRA Series

Contactors include a protective Forward/Reverse interlock for motor reversing and are ideal for applications

up to 2 Horse Power. For complete specifications, see DRA Series AC 3 Phase Contactors & DRA AC Motor

Reversing Contactors datasheets at www.crydom.com.

Install the contactor on the DIN rail as shown in fig. 1. Vertical

mounting operation is recommended.

If multiple units are installed be sure to follow derating curve (fig. 2).

DRA Series Contactors

(A)

(B)

(C)

(A,B)

Unless otherwise noted, all

ratings are at 0 mm air gap for

adjacent similar parts.

Resistive Load Current rating

for AC Control is 3.4 A @ 0 mm

air gap. For maximum ratings

use 45 mm air gap.

AC-53a rating for DRA3Pxxx2

(A, B & C suffix) is 0.55 KW @

480 VAC.

(D)

AC-53a rating for DRA3Pxxx2

(A, B & C suffix) is 0.37 KW @

480 VAC.

fig. 2

Derating Curve for 3 Phase & Motor Reversing contactor.

Temp.

40°C

1 HP (0.75 KW)

(C)

(D)

60°C

¾ HP (0.55 KW)

2 HP (0.75 KW)

1 HP (0.37 KW)

DRA3Pxxx2

DRA3Pxxx4

1 HP (0.75 KW)

¾ HP (0.55 KW)

2 HP (1.5 KW)

1 HP (0.75 KW)

DRA3Rxxx2

DRA3Rxxx4

Wire the contactor to the input control side following the

corresponding wiring diagram (fig. 3 or fig. 4). AWG #24 minimum,

AWG #12 maximum (0.2-3.3 mm

2

), choose wire gauge according to

load current. Maximum recommended terminal screw torque input

4.3 in-lbs (0.5 Nm).

Wire the contactor to the AC Line side (L1, L2 & L3) and to the Load

side (T1, T2 & T3). AWG #24 minimum, AWG #10 maximum (0.3-5.3

mm

2

), choose wire gauge according to load current. Maximum

recommended terminal screw torque output 12 in-lbs (1.37 Nm).

Series

Operating Voltage

40: 48-415 VAC

(Only for 3R)

48: 48-510 VAC

Rated Load Current

2: 2.4 Amp/

1HP @ 480 VAC

4: 4.2 Amp/

2HP @ 480 VAC

Control Voltage

D: 4-6 VDC

E: 18-28 VDC

A: 200-265 VAC

B: 90-140 VAC

C: 36-60 VAC

Function

3P: 3 Phase

3R: Reversible

Switching Type (Only for 3P)

Blank: Zero Voltage Turn-On

R: Instantaneous Turn-On

4

48

D

DRA

3P

R

Controlled Legs

(Only for 3P)

Blank: 3 Legs

2: 2 Legs

2

Installation Sheet

DIN Rail Mount

Do not forget to visit us at:

www.crydom.com

Copyright © 2014 Custom Sensors & Technologies. Specifications subject to change without notice.