CDXQ SERIES

Fan Coil Units

INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS

GENERAL

The manufacturer assumes no re-

sponsibility for equipment installed in
violation of any code requirement.

These instructions give information

relative to the installation of these fan
coil units only. For other related
equipment refer to the proper instruc-
tions.

Material in this shipment has been

inspected at the factory and released
to the transportation agency in good
condition. When received, a visual
inspection of all cartons should be
made immediately. Any evidence of
rough handling or apparent damage
should be noted on the delivery re-
ceipt and the material inspected in
the presence of the carrier’s repre-
sentative. If damage is found, a claim
should be filed against the carrier
immediately.

Note: State of MA.-248 CMR code of the
state of MA. requires a pump timer (60
seconds on every 6 hours). See dia-
gram.

FAN COIL UNIT

The installer must adhere strictly

****** WARNING ******

Unit must not be operated
during building construction
due to excessive airborne dust
and debris. The unit must not
be operated under any
circumstances without an air
filter in place.

to all local and national code require-
ments pertaining to the installation of
this equipment.

These units are designed for instal-

lation in a horizontal position.
The CDXQ is designed for free return
installation (non-ducted return air),
therefore the furred down area must
be completely sealed (except return
air grille) to ensure that all return air is
pulled from the conditioned space
and not from other areas of the build-
ing structure.
Access must be provided for servic-
ing the unit. If this access is provided
by a removable ceiling panel, ample
space must be allowed for removal of
the blower panel and to provide ac-
cess to electrical and plumbing con-
trols.
All CDXQ units are U.L. listed for
installation with zero inches clear-
ance to combustible materials. This
includes the unit cabinet, discharge
plenum and connecting ducts.

AIR DISTRIBUTION
DUCTS

All duct work must be installed in

accordance with National Fire Pro-
tection Association Codes 90A and
90B. Ducts should be adequately
insulated to prevent condensation
during the cooling cycle and to mini-
mize heat loss during the heating
cycle. All return air must be filtered to
prevent dirt buildup on the coil sur-
face. If there is no ducted return,
applicable installation codes may
limit the unit to installation only in a
single story residence. In many
cases it is acceptable to use ducting
of the same size as the fan coil
connections. However, unique ar-

rangements or long duct runs must be
confirmed by a local professional.
The manufacturer will not be respon-
sible for misapplied equipment.

ELECTRICAL

All wiring must comply with local

and national code requirements.
Units are provided with wiring dia-
grams and nameplate data to provide
information required for necessary
field wiring.
These units are provided with a
Class 2 transformer for 24-volt control
circuits. Should any add-on equip-

****** WARNING ******

Any devices such as fan
switches or thermostats that
have been furnished by the
factory for field installation
must be wired in strict accor-
dance with the wiring diagram
that is supplied with the unit.
Failure to do so could result
in damage to components
and will void all warranties.

L250 2/09

ment also have a Class 2 transformer
furnished, care must be taken to pre-
vent interconnecting outputs of the
two transformers by using a thermo-
stat with isolating contacts.

INSTALLATION
PRECAUTIONS

Installation of this fan coil should

only be performed by properly trained
personnel to ensure proper installa-
tion and the safety of the installer.

**WARNING TO INSTALLER, SERVICE PERSONNEL AND OWNER**

Altering the product or replacing parts with non authorized factory parts voids all warranty or implied warranty

and may result in adverse operational performance and/or a possible hazardous safety condition to service
personnel and occupants. Company employees and/or contractors are not authorized to waive this warning.
Current Maintenance Program is available at www.firstco.com under "Product Information".