Parameter value (pwe) 3rd and 4th word – Delta PROFIBUS-DP Module for VFD Series Drives PD-01 User Manual

Page 19

Advertising
background image

PD-01 PROFIBUS-DP Module

DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED

16

Fault numbers for "Cannot process request" response

NO. Meaning

0

Illegal Parameter number

Parameter does not exist

1

Parameter value cannot
be modified

Parameter is a read-only parameter
or can not change in current state

2

Minimum/maximum not
reached / exceeded

18 Other

error

IND

Structure of IND for cyclical communication via PPOs

PKE IND PWE1

PWE2

HIGH LOW HIGH LOW HIGH LOW HIGH LOW

15 14 13 12 11-8 7

0

Para Page selection Not used

2

0

2

3

2

2

2

1

0

Function of Parameter Page Selection

Basic PNU

(B.PNU bit 10-0 of PKE)

Page selection

(P.PNU)

Total PNU

(B.PNU+P.PNU*2000)

0…1999 0 0…1999

0…1999 1 2000…3999

0…1999 2 4000…4999

… …

0…1999 15

30000…31999

NOTE:
In IND, Bit 15 uses a multiplier of 2

0

, so the value of Bit 15 for the access P2000-

P3999 must be set to 1.

Parameter value (PWE) 3rd and 4th word

All parameters in VFD series Drives are 16-bit. A 16-bit parameter value is transferred
in PWE2 (4th word). PWE1 (3rd word) must be set to 0 on the PROFIBUS-DP master
in this case.