VCC-X Controller Technical Guide

MODGAS-X CONTROLLER WIRING

47

MODGAS-X Controller Wiring

MODGAS-X Controller Wiring

The OE377-26-00058 MODGAS-X Controller (AAON Part No.
V12090) is designed to modulate up to (2) gas valves to maintain
a desired Discharge Air Temperature. It also controls the speed of
the induced draft fan to maintain proper combustion in the heat
exchanger.

The MODGAS-X Controller directly connects to the VCC-

X Controller or indirectly using an E-BUS Expansion Board via an
EBC E-BUS cable. See Figure 32.

The following information will be passed between the MODGAS-X
controller and the VCC-X Controller:



Heat activation command

Heating Discharge Setpoint

Figure 32: MODGAS-X Controller to VCC-X Controller Wiring Diagram

MODGAS-X CONTROLLER

(OE377-26-00058)

Supply

Air Temperature

Sensor

Mount In Supply

Air Duct

Connect

to AI3 & GND

On VCC-X Controller

Supply Air Temperature

Sensor

EBC E-BUS Cable

Connects To

VCC-X Controller’s

Expansion

Port

Set Jumper To 1.

Fan Enable

Low Speed Fan

24 VAC Power
Input Terminals
Max. Power
Consumption
1 Gas Valve
= 18 VA
2 Gas Valves
= 33 VA

Aux Heat Valve

The offset for the Supply Air Temperature Sensor

High Limit Temperature Setpoint



If the communication is interrupted between the

MODGAS-X Controller and the VCC-X Controller,

the MODGAS-X controller will revert to stand-alone

operation.

For more information, refer to the MODGAS-X Controller Technical
Guide.

NOTE:

If using multiple E-BUS Sensors or Modules, the

E-BUS Hub or Adapter Board may be required.