Sloan Xlerator HAND DRYER User Manual

Installation instructions for xlerator, Hand dryer, Prior to installation

Advertising
background image

Code No. 0816786

Rev. 1 (06/10)

INSTALLATION INSTRUCTIONS

FOR XLERATOR

®

HAND DRYER

Prior to installing the Sloan OPTIMA XLerator

®

Electronic Hand Dryer,

determine the location where the dryer will be installed. Read the
following section entitled “Installation Precautions” and then refer to
Table 1 for recommended mounting heights.

Installation Precautions

• Mounting surface should be smooth and flat.
• Mount dryer at least 24 inches (610 mm) away from basins.
• Mount dryer at least 20 inches (508 mm) away from corners.
• Mount multiple hand dryers a minimum of 20 inches (508 mm)

apart, center to center.

• Avoid installing hand dryers in narrow hallways and behind swinging

doors.

Important:

INSTALL ALL ELECTRICAL WIRING IN ACCORDANCE WITH
NATIONAL/LOCAL CODES AND REGULATIONS.

Table 1 — Recommended Mounting Heights

Users

Height

Men

45 Inches (1143 mm)

Women

43 Inches (1092 mm)

Teenagers

41 Inches (1041 mm)

Small Children

35 Inches (889 mm)

Handicapped

37 Inches (940 mm)

Important: When Mounting over a countertop, distance between
counter and dryer MUST BE 15” (381 mm) MINIMUM.
Refer to Table 2 for recommended fasteners.

LIMITED WARRANTY

Sloan Valve Company warrants its XLerator

®

Hand Dryer to be made of first class materials, free from defects of material or workmanship under normal use and to

perform the service for which it is intended in a thoroughly reliable and efficient manner when properly installed and serviced, for a period of five years (1 year for
special finishes) from date of purchase. During this period, Sloan Valve Company will, at its option, repair or replace any part or parts which prove to be thus defective
if returned to Sloan Valve Company, at customer’s cost, and this shall be the sole remedy available under this warranty. No claims will be allowed for labor,
transportation or other incidental costs. This warranty extends only to persons or organizations who purchase Sloan Valve Company’s products directly from Sloan
Valve Company for purpose of resale.

THERE ARE NO WARRANTIES WHICH EXTEND BEYOND THE DESCRIPTION ON THE FACE HEREOF. IN NO EVENT IS SLOAN VALVE COMPANY RESPONSIBLE FOR
ANY CONSEQUENTIAL DAMAGES OF ANY MEASURE WHATSOEVER.

Step 1 — Remove Cover

Using wrench provided, remove two tamper-proof fasteners from sides
of dryer cover. Remove cover from dryer.

Step 2 — Attach Wall Plate to Wall

Attach wall plate to wall using the recommended fasteners shown in
Table 2. Install a fastener at each corner of the wall plate. In locations
where vandalism is a concern, install two additional mounting fasteners
at the locations shown in the rough-in on page 2. Remove control
assembly to access the right side mounting hole.

Step 3 — Connect Electrical Wiring

Connect a 110/120V dryer to a 15 Amp. branch circuit using at least
#12 GA copper wire. (Do not exceed a 20 Amp. branch circuit).
Connect a 220/240V dryer to no more than a 15 Amp. branch circuit
using at least a #14 GA copper wire. Attach lines to terminals as
indicated by the schematic inside dryer cover. Be sure that an
equipment ground wire is securely fastened to green ground screw on
base plate. For runs over 50 feet or for multiple installations, increase
the size of the wire used. Dryers located in shower rooms or other wet
locations should be installed with circuits protected by ground fault
interrupter(s) or as local codes require.

Step 4 — Replace Cover

For multiple installations, before replacing cover, check the Serial
Number marked inside the dryer to be sure it matches the Serial
Number marked on the label at the bottom of cover. DO NOT SWITCH
COVERS. Install Cover using the two tamper-proof fasteners.

Leave the special TAMPER PROOF WRENCH with the owner.

NOTE: If the dryer will not turn on, stays on or stops working, it may be mounted

too close to a counter or object. Turn off power to dryer for 10 seconds
and then reapply power. If dryer starts, then turn off again, relocate the
object or remount dryer. If this is not possible, adjust the range of the
sensor by turning the potentiometer on the control board clockwise to
decrease sensor range. Please contact the Sloan Installation Engineering
Department at 1-888-SLOAN-14 (1-888-756-2614) and one of our
trained technicians will be happy to assist you.

(Continued on Page 2)

PRIOR TO INSTALLATION

Table 2 — Recommended Fasteners

Wall Type

Recommended Fastener

Masonry Wall

1/2” expansion sleeve with 1/4” lag bolt

Hollow Wall

1/4” wing type through bolt

Wooden Wall

1/4” lag screw with washer

INSTALLATION INSTRUCTIONS

Advertising