8) lts series - attaching draft inducer assembly – Space Ray LTS Series Two Stage User Manual

Page 28

Advertising
background image

Form #43155040
May 2013

-27-

Tube Flange

12 Radial Hole for 40-200M BTU units only

6 Hole for 225-250M BTU units only

MPT Gas

Pipe Connection

Reflector

1/4-20 Locknut

(QTY-3 per flange)

Tube Flange

Gasket

3/8” Connector

(24V wire leads from

draft inducer to

L1 and L2 of the

control box terminal block)

Control Box

Perforated

Fresh Air Plate

Burner

Sight Glass

Nameplate/

Rating Label

Clearances to

Combustibles

Label

Access

Panel

Note: The wiring connection

diagram is located on the inside

access panel and inside the

junction box panel.

4.

The heater can be mounted horizontally

horizontally

horizontally

horizontally or at an angle of up to 45 degrees

45 degrees

45 degrees

45 degrees maximum from horizontal.

When angle mounting, the control box

control box

control box

control box must be positioned upright

upright

upright

upright. F

F

F

Failure to install the control box in an

ailure to install the control box in an

ailure to install the control box in an

ailure to install the control box in an

upright position will VOID the manufacturer

upright position will VOID the manufacturer

upright position will VOID the manufacturer

upright position will VOID the manufacturer’s warranty

’s warranty

’s warranty

’s warranty.... For additional instructions see Section 13.0) for

multiple hanging and draft inducer positions.

11.8)

LTS SERIES - ATTACHING DRAFT INDUCER ASSEMBLY

1.

Attach the draft inducer assembly and gasket to end of the draft inducer flange and secure with 1/4-20

locknuts. A flue restrictor plate is attached to the draft inducer weld studs. DO NOT DISCARD

DO NOT DISCARD

DO NOT DISCARD

DO NOT DISCARD

RESTRICTOR PLATE

RESTRICTOR PLATE

RESTRICTOR PLATE

RESTRICTOR PLATE and make sure this remains in place while the draft inducer is being attached to the
heater body. NOTE:

NOTE:

NOTE:

NOTE: The draft inducer can be mounted in a vertical, a 45º, or a horizontal position. Refer

to Section 13.0).

2.

Disconnect the piece of SJO cable (if equipped) from the junction box and discard. This is used only on

LTU series heaters.

3.

The 3/8" connector used to hold the SJO cable will remain to provide strain relief for field wiring of the

control box and the draft inducer (refer to the Electrical Connections and Connection Wiring Diagram for
wiring between the control box and the draft inducer in Section 16.0).

4.

If the heater is to be VENTED to the outside of the building, place the starting collar on the outlet of the

draft inducer and secure with the #8-32 screws and nuts. Place the flue pipe directly onto the starting
collar, secure with the #8 sheet metal screws, and terminate with an approved vent cap.

5.

If the heater is for UNVENTED use, place the exhaust hood (supplied as an accessory) directly onto the

outlet of the draft inducer (starting collar is not necessary for unvented use). Secure with the #8 sheet
metal screws. The exhaust hood must be mounted only in an upright position and directed toward the

The exhaust hood must be mounted only in an upright position and directed toward the

The exhaust hood must be mounted only in an upright position and directed toward the

The exhaust hood must be mounted only in an upright position and directed toward the

reflector body.

reflector body.

reflector body.

reflector body.