Multiple Heater Horizontal Venting Arrangement

4” diameter

single wall vent

Plan View

Vent Cap

2” (5cm)

Clearance

Thimble

6” (15cm)

minimum

Y Connector

4” diameter

single wall vent

2” (5cm)

Clearance

Thimble

no less than 1/4” (6mm)

rise per foot (0.3m)

toward vent terminal

6” (15cm)

minimum

Y Connector

See Vent

Sizing Table

for diameter

See Vent

Sizing Table

for diameter

no less than 1/4” (6mm)

rise per foot (0.3m)

toward vent terminal

Multiple Heater Venting (Connections into a Manifold)

Total

vent

height

Connector

rise

VENT SIZING TABLE

VENT SIZING TABLE

VENT SIZING TABLE

VENT SIZING TABLE —

Multiple Heater Venting

Multiple Heater Venting

Multiple Heater Venting

Multiple Heater Venting

Number of Heaters

Number of Heaters

Number of Heaters

Number of Heaters

1

1

1

1

2

2

2

2

3

3

3

3

4

4

4

4

5

5

5

5

LTU40-50

4”

4”

5”

5”

6”

LTU60-75

4”

5”

6”

6”

7”

LTS/U80-100

4”

6”

6”

7”

8”

LTS/U110-130

4”

6”

7”

8”

9”

LTS/U140-175

4”

6”

8”

9”

10”

LTS/U180-200

6”

8”

9”

10”

11”

LTS/U225-250

6”

9”

10”

11”

12”

COMMON VENT DIAMETER

COMMON VENT DIAMETER

COMMON VENT DIAMETER

COMMON VENT DIAMETER

(If a size is not available use the next larger size.)

THE ABOVE ILLUSTRATIONS AND TABLE OF VENT SIZES FOR COMMON VENTING OF MULTIPLE HEATERS ARE IN
ACCORDANCE WITH THE NATIONAL FUEL GAS CODE ANSI Z223.1-LATEST EDITION, NFPA 54-LATEST EDITION, EQUIPMENT
VOLUME OF 1988 ASHRAE HANDBOOK, CURRENT CAN/CGA-B149.1/2-M86 INSTALLATION CODE, AND AGA PUBLICATION
NO. 10M5.85 2.5-2 ON FUNDAMENTALS OF GAS APPLIANCE VENTING AND VENTILATION-REVISED BUT ARE NOT A PART OF
THE CSA CERTIFICATION.