5) motor and blower wheel check, 0) installation data – Space Ray LTS Series Two Stage User Manual

Page 56

Advertising
background image

Form #43155040
May 2013

-55-

IGNITION MODULE DIAGNOSTICS

IGNITION MODULE DIAGNOSTICS

IGNITION MODULE DIAGNOSTICS

IGNITION MODULE DIAGNOSTICS

(Fenwal #35

(Fenwal #35

(Fenwal #35

(Fenwal #35----6087J1

6087J1

6087J1

6087J1----034 module only)

034 module only)

034 module only)

034 module only)

The LED

LED

LED

LED located on the ignition module will flash ON

ON

ON

ON for ¼ second, then OFF

OFF

OFF

OFF for ¼ second during a fault

condition. The pause between fault codes is 3 seconds.

LED Indication

Error Mode

Steady On

Internal Control Fault

2 Flashes

Flame Sense Fault

3 Flashes

Ignition Lockout



TO CHECK FLAME SENSOR CIRCUIT

TO CHECK FLAME SENSOR CIRCUIT

TO CHECK FLAME SENSOR CIRCUIT

TO CHECK FLAME SENSOR CIRCUIT

(Fenwal #35

(Fenwal #35

(Fenwal #35

(Fenwal #35----6087J1

6087J1

6087J1

6087J1----034 module only)

034 module only)

034 module only)

034 module only)

The flame current is the current that passes through the flame from the sensor to the ground. The
minimum flame current necessary to keep the system from lockout is 0.7

0.7

0.7

0.7 micro-amps.

a.

To measure the flame current, connect an analog DC micro-ammeter to the FC

FC

FC

FC---- and FC+

FC+

FC+

FC+ terminals per

diagram. The meter should read 0.7

0.7

0.7

0.7 micro-amps or higher when the burner is running full on.


b.

If the meter reads below zero

zero

zero

zero, the meter leads are reversed. Disconnect power and reconnect the meter

leads for proper polarity.


c.

Remove micro-ammeter. Return system to normal operation.

MULTIPURPOSE METER

USE

MICROAMP

SCALE

BLACK (-)

RED (+)

LED Display

VALVE
GND

(BURNER)

FC-
FC+

VALVE

25V

Ignition Module - Alternate

(Fenwal #35-6087J1-034)

24.5)

MOTOR AND BLOWER WHEEL CHECK

If draft inducer motor fails to run:

a.

Check power supply to junction box.

b.

Check for loose or broken motor lead wire.

c.

Check to see that blower wheel turns freely and is not rubbing housing. Blower wheel may have worked

loose from shaft and jammed against housing.

d.

Check for blower wheel damage; replace if necessary. If no damage, readjust blower wheel on shaft &

retighten set screw.

e.

If all above does not correct, replace motor.

25.0)