Installation & Maintenance Instructions for

Bestobell Steam TT2/TT3 Series Total Trap

®

Stations

Warning: Bestobell Steam products must only be used, installed and repaired in accordance with these Installation & Maintenance Instructions.

Observe all applicable public and company codes and regulations. In the event of leakage or other malfunction, call a qualified service person;

continued operation may cause system failure or a general hazard. Prior to servicing equipment, disconnect, shut off, drain and/or bypass all pres-

surized fluids.

Please Read These Instructions

The Total Trap

®

2 & 3 Series will provide you with long, trou-

ble-free service if it is correctly installed and maintained. A

few minutes of your time spent reading these instructions

may save hours of trouble and downtime later.

Ideal Installation

1. To protect the trap from grit, scale, metal chips,

and other foreign matter, ALL pipelines and piping

components should be blown out and thoroughly

cleaned before the trap is installed.

2. In preparing welded connections, care should be

exercised to prevent debris, fluids or compound

from getting into pipe lines.

3. The flow arrow on the trap body must be pointed

in the direction of flow. Ideally, the trap should be

installed in the lowest horizontal line of downcomer

piping to provide for maximum drainage of conden-

sate and to obtain a faster response by the disc trap.

4. The trap should be installed horizontally with disc

trap cap on top. The outlet of the blowdown valve

on the bottom of the trap should be connected to

blowdown piping to adequately route high tempera-

ture/pressure steam away from personnel and other

equipment that could be damaged. The vent on the

back of the trap should similarly be oriented away

from personnel and other equipment that could be

damaged.

5. Piping should be the same material and sized ap-

propriately for the hub end connections. Inlet and

outlet piping should be the same size.

6. A full-ported shutoff valve upstream is recommend-

ed to allow isolation for servicing. A shutoff valve

downstream will protect against back flow from the

return line during servicing. Alternately, the isolation

valves built into the trap can be used to adequately

isolate the disc trap assembly for maintenance pur-

poses provided the trap is isolated upstream and/or

the system is in a cold iron state, i.e. shutdown.

7. The downcomer piping should be sloped to and

from the trap to ensure adequate flow and freeze

protection.

Start and Initial Warm-Up

1. Fully open the inlet and outlet isolation valves.

2. Fully close the freeblow/vent, strainer blowdown, and

bypass valves.

3. Slowly apply system pressure to steam trap and

bring system up to operating conditions per customer

usual start-up procedures.

Caution!

The strainer blowdown valve achieves maximum
sealing properties when heated up. A slight amount
of steam leak-by during start-up from the blowdown
valve may be noticed until the valve packing heats
enough, at which point leak-by should cease.

Maintenance

Warning!

Hot discharge from the trap may cause severe burns.
Shut off steam supply and make sure that the trap is
cool to the touch before conducting maintenance or
inspection.

Caution!

Do not remove the flush plug above the steam inlet hub
unless the system is shut-down, the trap is cool to the
touch, and the intent is to clean the disc trap assembly
through back flushing. If debris has not been allowed
to enter the steam system, cleaning of the disc trap
assembly and removal of the flush plug should not be
necessary.

1. The trap can be maintained without disturbing the

piping connections. Ensure that the trap is isolated -

upstream and downstream - before attempting

any maintenance involving disassembly of the disc

trap. ALLOW THE TRAP TO COOL BEFORE

DISASSEMBLY.