Humidity, Cleanness, Table 1 – H3C Technologies H3C S10500 Series Switches User Manual

Page 11

Advertising
background image

3

Table 1 Temperature requirements

Temperature Range

Operating temperature

0°C to 45°C (32°F to 113°F)

Storage temperature

–40°C to +70°C (–40°F to +158°F)

Humidity

Maintain appropriate humidity in your equipment room, as described in

Table 2

.

Lasting high relative humidity tends to cause poor insulation, electricity creepage, mechanical
property change of materials, and corrosion of metal parts.

Lasting low relative humidity is likely to result in loose screws due to washer contraction, and even
electrostatic discharge (ESD), which causes the circuits to fail.

Table 2 Humidity requirements

Humidity Range

Operating humidity

10% to 95%, noncondensing

Storage humidity

5% to 95%, noncondensing

Cleanness

Dust buildup on the chassis might result in electrostatic adsorption, which causes poor contact of metal

components and contact points. In the worst case, electrostatic adsorption can cause communication

failure.

Table 3 Dust concentration limit in the equipment room

Substance

Concentration limit (particles/m

3

)

Dust particles

≤ 3 x 10

4

(No visible dust on desk in three days)

NOTE:

Dust particle diameter ≥ 5 μm

The equipment room must also meet strict limits on salts, acids, and sulfides to eliminate corrosion and

premature aging of components, as shown in

Table 4

.

Table 4 Harmful gas limits in an equipment room

Gas Max.

(mg/m

3

)

SO

2

0.2

H

2

S 0.006

NH

3

0.05

Cl

2

0.01