Retrotec DU200 DucTester Testing Procedures to meet EnergyStar Standards User Manual

Retrotec Measuring instruments

Advertising
background image

Page 1 of 4

PR115

rev-2011-09-02

4.1

Total measured duct leakage to meet ENERGY STAR standards







1. With air-handler off, connect DucTester with

Mid-Range plate, and seal registers.

2. On the DM-2* digital gauge:

a. Press [Mode] until “cfm/100ft

2

” appears.

If unavailable, press [Setup], “Mode Setup”.

b. Press [Device] to get “Retrotec DU200”
c. Press [Range Config] to get "Mid".

*See page 4 for Setup instructions.

3. Press [Enter

Area

], input the conditioned floor

area, press [Enter], for each house.

4. Press [Set Pressure] [25] [Enter].
5. Press the [@] key until “@ 25 Pa” is displayed.
6. Leakage must be corrected if above 6.

Measure leakage to outdoors if above 4.

CFM at 25 Pa per 100 sq. ft.

Floor area, sq. ft.

>8 fail, >5 test to outdoors

Less than 1200

>6 fail, >4 test to outdoors

More than 1200





This test measures
total duct leakage in
CFM25 per 100 sq. ft.
of conditioned floor
area.












Pink denotes
pressurized area

Advertising