Hardware and Components

Two sizes of enclosures provide flexibility and expansion to meet evolving application needs. Both sizes of

enclosures come standard with a liquid crystal display (LCD) and controller board. In addition, the large

Universal Monitor has an internal Transformer Module.
The enclosure features a key lock for added security and is made of metal to accommodate secure conduit

fittings and protect components against environmental debris. The enclosure is designed for easy wire

routing and terminations, with top and bottom access slots for communication cables and network wires. The

enclosure is 2-3/4" deep, allowing for recess mounting in a wall.

Keypad Display

The keypad display is a user

interface mounted on the

enclosure door of each Universal

Monitor. The display provides

for complete monitoring and

configuration of the panel and is

password-protected.
The keypad display provides the ability for the

Universal Monitor to operate as a complete

standalone panel.

Controller Board

The controller board supports 22 points:
• Eight digital inputs
• Four analog inputs
• Eight digital outputs
• Two Common Alarm outputs
The digital inputs are dry contacts. The analog

inputs are 4-20mA inputs. The digital outputs and

Common Alarm outputs are Form C contact relays.
The point terminations are made using removable

terminal blocks. This allows for easier access to the

terminators, streamlining the process of connecting

external devices to the Universal Monitor.
The battery supplies power to the modem for a mini-

mum of 10 minutes, providing the capability to send

out a loss-of-power alarm to all configured pagers.
Flash ROM may be easily upgraded at the job site,

simplifying the process of installing new firmware as

it becomes available.
An RS232 operator terminal port is included with

each controller board for easy interface to a laptop or

desktop PC for setup and device monitoring.
An integrated on-board modem is included with each

controller board for remote access to the Universal

Monitor. An RJ11 phone modem jack is also

included. The modem is factory-configured, eliminat-

ing field configuration and wiring requirements.
An IGM422 connection is included with each control-

ler to connect the Universal Monitor to Liebert’s

SiteScan Web Enterprise Monitoring System. This

connection allows information and alarms to be mon-

itored from a centrally located command center.

Transformer Module

The large Universal Monitor

comes with either 115VAC or

230VAC Transformer Module.
• The 115VAC Transformer

Module provides step-down

power from 115VAC to

24VAC, two Class 2 24VAC

40VA power terminations

and one 115VAC outlet to

power accessory devices,

such as a Portable Operator’s

Terminal.

• The 230VAC Transformer

Module provides step-down power from 230VAC

to 24VAC and two Class 2 24VAC 40VA power ter-

minations. An outlet is not provided on this Trans-

former Module.

The Transformer Module may be ordered separately

as an option for the small Universal Monitor—or any

device requiring 24VAC—and mounted outside the

enclosure.

I/O Expansion Module

The Universal Monitor I/O Expansion Module, pur-

chased separately, has connectors for 16 digital

inputs and eight digital outputs, as shown below.

The board has light emitting diodes (LEDs) to dis-

play the status of monitored output devices, commu-

nications ports for connection to the Universal

Monitor, power connections and other features nec-

essary to monitor and protect your operation.

Keypad

115VAC Transformer

230VAC Transformer

OUT1

K1

V1

V3

V5

V7

V9

V11

V13

V15

V2

V4

V6

V8

V10

V12

V14

V16

K2

K3

K4

K5

K6

K7

K8

OUT2

OUT3

OUT4

OUT5

OUT6

OUT7

OUT8

S4

S3

S2

S1

Multiflex 168AO

810-3065

DEFAULT SETTINGS FOR USE WITH UNIVERSAL MONITOR

USE COPPER (CU) CONDUCTORS ONLY.

D6

POWER INPUT

EIA485 + (to UM-)

0V

EIA485 - (to UM+)

RELAY OUTPUTS

24VAC power

connector

Digital

output

fuses (8)

Digital

output

DIP

switch

Digital input connectors (16)

EIA485 connector

Digital output

connectors (8)

I/O Expansion Module Components

& Key Features