Troubleshooting and reconnecting wires to the “compressor capacitor” on the

AP550Z


Tools required:
Phillips screwdriver

The problem:
If the AP550Z was recently shipped or roughly moved, it may have one of two problems:

• The fan to the interior of the room turns on, but the air blown out of it is room

temperature. Or,

• The unit blows the circuit breaker it is run on


Warnings:

Make sure the unit is disconnected from the power supply prior to working

on it

• Do not attempt this repair if you do not feel comfortable with any procedures

• If you require any assistance, please call EdgeStar Service at 866-319-5473


The repair:

1. Make sure the unit is unplugged
2. Face the rear of the unit
3. Remove the filter frame:

it

it

Pull up on the
filter frame, then
pull down and
away from the un
to remove