Emerson LIQUI-TECT LT410 User Manual

Point leak detection sensor, Iqui, Tect

Advertising
background image

Product Specification Sheet

page 1

11/02 (Rev. 0)

L

IQUI

-

TECT®

410

Point Leak Detection Sensor

Description

The Liqui-tect 410

(LT410) provides a

single-point detection

of leaks. The point

detection sensor has

two gold-plated

sensing probes to

prevent corrosion

resistance and to

provide accurate

readings. The LT410

constantly monitors

points for leaks,

internal faults and power failures and warns of any

abnormal conditions. Mounting brackets allow for

sensor height adjustment and leveling.
The LT410 is the ideal solution for sensing leaks under

a raised computer floor or air conditioning drip pans.

Two independent outputs provide added flexibility

with the capacity to signal both a local alarm panel

and a remote building management system or external

equipment, such as motorized water shut-off valves.
The LT410 is also ideally suited for the following:

Placement on Subfloor

Under Cooling Support Equipment

Specifications

Dimensions-Top, Front & Side Views

Wiring Interconnections

Ordering Information

Applications

Locations

• Glycol, Chilled

Water Cooling

• Humidification

Feed Water Piping

• Condensate Pumps

and Drains

• Unit and Ceiling

Auxiliary Drip Pans

• Overhead Piping

Troughs

• Large-Scale Network Control

Centers

• Data Centers
• Server Rooms - Closets
• Unattended Remote Shelters
• Mechanical Equipment Rooms
• Sensitive Areas With

Overhead Piping

• Industrial Process Control

Rooms

* Output connections to external alarm monitoring panels

such as the Liebert contact closure alarm panels

Leak detection

zone (directly

beneath unit)

To a Liebert

environmental

unit and

an optional*

monitoring

panel

To external

power

supply or

directly

from

unit

LT410

Liqui-tect 410 Sensor
Power requirements

24 VAC 100 mA, 50/60 Hz, 3 VA (max.)

Dimensions

W x D x H

6.35" x 2.25" x 4.46"

(161.2 mm x 57.2 mm x 113.2 mm)

Weight (assembled)

2.0 lbs (0.9 kg)

Metal enclosure

NEMA 1, IP 30

Environmental Conditions
Operating temperature

50°F to 104°F (10°C to 40°C)

Operating humidity

10% to 95% relative humidity

(non-condensing)

Operating altitude

0 to 10,000 ft (0 to 3,048 m)

Output Relays
Contact rating

2 Form-C; 3 A rating at 24 VAC

Agency Listings
UL

UL916

C-UL

C22.2, No. 205-M1983

CE

Yes

FCC Compliance

47 CFR, Part 15

Red Wires

Orange Wires

Yellow Wires

24 V, AC/DC

@0.10A, 50-60Hz, DC

Class 2 Circuit Only

Alarm Contact Rating

24 VAC @ 3A

Class 2 Circuit Only

Alarm Contact Rating

24 VAC @ 3A

Class 2 Circuit Only

Product

Number

Quantity

Description

LT410

Point Leak Detection Sensor

5.85"

(148.5mm)

TOP VIEW

Form-C relay

outputs &

power wiring

connection

4.46"

(113.2mm)

FRONT VIEW

Adjustable

probe height

0.0–0.5"

(0.0–12.7mm)

2.25"

(57.2mm)

SIDE VIEW

6.35"

(161.2mm)

Shipping weight: 2 Ibs (0.9 kg)

Mounting holes: #8 screws

Po

w

er

Po

w

er

1-

N

O

1-

N

C

1-

C

O

M

2-

N

O

2-

N

C

2-

C

O

M

Gold-plated

probes

Height adjustable

0-0.5" (0-12.7mm)