G. Installation of Remote Condenser Unit

WARNING

1. Installation of the remote condenser unit must be performed by properly

trained and EPA-certified service personnel.

2. The remote condenser unit must be installed in accordance with applicable

national, state, and local codes and regulations.

3. Failure to install the equipment within these guidelines may adversely affect

safety, performance, component life, and warranty coverage.

4. Power supply and ground wire to the remote condenser unit are supplied

from the icemaker. For details, see section "II.G.6. Electrical Connection."

1. Checks Before Installation

1) Remove the shipping carton, tape, and packing material.
2) Check that the refrigerant lines do not rub or touch lines or other surfaces, and that the

fan blades move freely.

2. Location

CAUTION

The remote condenser unit is intended for outdoor use. Normal operating
ambient temperature should be within -20°F to +122°F (-29°C to +50°C).
Operation of the remote condenser unit, for extended periods, outside of this
normal temperature range may affect icemaker performance.

The remote condenser unit must be positioned in a permanent site under the following
guidelines:

• A firm and flat site.
• A dry and well ventilated area with 24" (61

cm) clearance in both front and rear for
ease of maintenance and/or service should
they be required. See Fig. 9.

• The maximum line length for the standard

refrigerant charge is 66 feet. With
additional refrigerant, the maximum line
length is 100 feet. For details, see "II.G.5.
Refrigerant Charge (Line Set Exceeding
66 Feet)."

• The maximum vertical distance between

the remote condenser unit and the
icemaker is 33 feet above or 10 feet
below the icemaker. These distances are
measured fitting to fitting. See Fig. 10.

Air

Fig. 9

Min. 24" (61 cm) Clearance

Air

Fig. 10

Icemaker

Remote

Condenser

Unit

Service Loop

Max. 33 Feet