International Electrotechnical Commission (IEC)
Classification of Hazardous Locations,

Continued

IEC Temperature
Classification

Equipment intended for installation directly within the hazardous
location must also be classified for the maximum surface temperature
that can be generated under normal or fault conditions as referenced to
the maximum operating ambient of the equipment. The maximum
surface temperature must be less than the minimum autoignition
temperature of the hazardous atmosphere present. The temperature shall
be indicated in identification numbers as listed in the following table.

Maximum

Temperature

Degrees C

Degrees F

Identification Number

450 842 T1

300 572 T2

200 392 T3

135 275 T4

100 212 T5

85 185 T6

Certification and
Conformity Details

Table B-3

CENELEC / LCIE Certification

Code Description

3D

Flameproof, Supply

≤ 45 Vdc, IP 66/67EEx d IIC T6.

3A

Intrinsically Safe EEx ia IIC T5,

−40 ≤ Ta ≤ 93°C.

Flameproof, Supply

≤ 45 Vdc, IP 66/67 EEx d IIC T6.

LCIE Intrinsic Safety Parameters

(1)

U

i

= 30 V

I

i

= 100 mA

P

i

= 1.2 W

C

i

= 4.2 nF

R

i

= 0

L

i

= 0

With no integral indicator, or with
integral Smart Meter, option SM.

L

i

= 150

µH

With Analog Meter, option ME.

(1)

Install in accordance with Honeywell drawing 51204243.