2.1

Connecting Power and SCT/SFC,

Continued

CAUTION

Do not try to remove the transmitter housing end-cap before loosening the
end-cap lock on the transmitter housing.

Table 1

Connecting Power Supply and SFC to ST 3000

Step Action

1

Use a 1.5 mm allen wrench to loosen the end-cap lock on the
terminal side of the transmitter housing. Unscrew and remove the
end cap from the housing

2

If the transmitter is supplied with an optional integral analog meter,
unsnap the meter from the terminal block to expose the wiring
connections.

3

Observing polarity, connect a 25 Vdc power supply to the
transmitter’s SIGNAL terminals as shown in Figure 1.

ATTENTION Be sure there is a minimum of 250 ohms resistance

between the power supply and the transmitter.

4

Connect the SCT or SFC to the transmitter - red lead to SIGNAL
positive and black lead to SIGNAL negative. See Figure 1.

5

• If you are using the SCT, Select Tag ID icon from the SCT
toolbar to establish on-line commnications with the transmitter.

• If you are using the SFC, go to Section 2.2.

Figure 1

Typical Power Supply and SCT/SFC Connections to ST 3000.

Easy connect terminals
for direct SCT or SFC

connections

-

S

IG

N

A

L

+

+

-

T

E

S

T

250

25 Vdc
Power
Supply

+

-

+ Red

- Black

ST 3000

SCT

SFC

6