Table 9, Zero corrects procedure for std110 – Honeywell ST 3000 User Manual

Page 38

Advertising
background image

4.1

Mounting ST 3000 Transmitter,

Continued

Precautions for
Mounting
Transmitters with
Small Absolute or
Differential Pressure
Spans,
continued

For a transmitter with a small differential pressure span, you must
ensure that the transmitter is vertical when mounting it. You do this by
leveling the transmitter side-to-side and front-to-back. See Figure 6 for
suggestions on how to level the transmitter using a spirit balance. You
must also zero the transmitter by following the steps in Table 9 below.

Table 9

Zero Corrects Procedure for STD110

Step Action

1

Attach the transmitter to the mounting bracket but do not completely
tighten the mounting bolts

2

Connect a tube between the input connections in the high pressure
(HP) and low pressure (LP) heads to eliminate the affects of any
surrounding air currents.

3

Connect 24 Vdc power to the transmitter and connect a digital
voltmeter or SFC to read the transmitter’s output. See Figure 1 for
typical SFC connection or connect a voltmeter across the 250 ohm
resistor, if desired.

4

Use the SFC (or SCT) and establish communications with the
transmitter. Follow the steps in Table 2, if needed.

5

While reading the transmitter’s output on an SFC or a voltmeter,
position the transmitter so the output reading is at or near zero and
then completely tighten the mounting bolts.

6

Do an input zero correct function using the SFC and following the
steps below. This corrects the transmitter for any minor error that
may occur after the mounting bolts are tightened.

7

Initiate shift key selection. Press

^

SHIFT

key

Press

INPUT

J

OUT-
PUT

key. Read applied input pressure.

Press

RESET

K

COR-
RECT

key. Prompt asks if the applied input pressure equals

zero input. If it is zero input, go to next keystroke. If it is not, press
[

CLR

] key to exit function and repeat keystrokes.

Press

NON-VOL

ENTER

(Yes)

key. Zero input is set equal to applied input pressure.

8

Remove the tube from between the input connections, the power,
and the digital voltmeter or SFC.

9

Continue with the remaining installation tasks.

Continued on next page

28

ST 3000 Release 300 Installation Guide

2/05

Advertising