Table 10, Mounting remote diaphragm seal transmitter – Honeywell ST 3000 User Manual

Page 42

Advertising
background image

4.1

Mounting ST 3000 Transmitter,

Continued

Remote seal
mounting

Use the procedure in Table 10 to mount a remote diaphragm seal
transmitter model. Figure 10 shows a typical installation for a remote
diaphragm seal transmitter for reference.

ATTENTION

Mount the transmitter flanges within the limits stated here for the given
fill-fluid in the capillary tubes with a tank at one atmosphere.

IF the fill fluid is…

THEN mount the flange…

Silicone DC 200 Oil

no greater than 22 feet (6.7 meters)
below the transmitter

Silicone DC 704 Oil

no greater than 19 feet (5.8 meters)
below the transmitter

Chlorotrifluorethylene no

greater than 11 feet (3.4 meters)

below the transmitter.


NOTE: The combination of tank vacuum and high pressure capillary

head effect should not exceed 9 psi (300 mm Hg) absolute.


Table 10

Mounting Remote Diaphragm Seal Transmitter

Step Action

1

Mount transmitter at a remote distance determined by length of
capillary tubing.

2

If Transmitter Model

Then Connect Remote

Number is…

Seal on…

STR93D or STR12D

high pressure (HP) side of

transmitter to lower flange

mounting on tank wall for

variable head H1.

STR13D

low pressure (LP) side of

transmitter to lower flange

mounting on tank wall for

variable head H1.

ATTENTION On insulated tanks, remove enough insulation to

accommodate the flange extension.

Continued on next page

32

ST 3000 Release 300 Installation Guide