background image

4.1

Mounting ST 3000 Transmitter,

Continued

Remote seal
mounting,
continued


Table 10

Mounting Remote Diaphragm Seal Transmitter, continued

Step Action

3

If Transmitter Model

Then Connect Remote

Number is…

Seal on…

STR93D or STR12D

low pressure (LP) side of

transmitter to upper flange

mounting on tank wall for

fixed or constant head H2.

STR13D

high pressure (HP) side of

transmitter to upper flange

mounting on tank wall for

fixed or constant head H2.

*

ATTENTION On insulated tanks, remove enough insulation to

accommodate the flange extension.

4

It is the End User’s responsibility to provide a flange gasket and

mounting hardware that are suitable for the transmitter’s service
condition


Figure 10

Typical Remote Diaphragm Seal Transmitter Installation.

Variable
Head H1

HP Side
- Model STR93D
- Model STR12D

LP Side
- Model STR13D

Minimum Level

Maximum Level

LP Side
- Model STR93D
- Model STR12D

HP Side
- Model STR13D

H2

Fixed

Ref. Leg

2/05

ST 3000 Release 300 Installation Guide

33