Table 14, Installing flange adapter – Honeywell ST 3000 User Manual

Page 48

Advertising
background image

4.2

Piping ST 3000 Transmitter,

Continued

Installing flange
adapter

Table 14 gives the steps for an optional flange adapter on the process
head.

ATTENTION

Slightly deforming the gasket supplied with the adapter before you
insert it into the adapter may aid in retaining the gasket in the groove
while you align the adapter to the process head. To deform the gasket,
submerse it in hot water for a few minutes then firmly press it into its
recessed mounting groove in the adapter.

Table

14 Installing

Flange

Adapter

Step Action

1

Insert filter screen (if supplied) into inlet cavity of process head.

2

Carefully seat Teflon (white) gasket into adapter groove.

3

Thread adapter onto 1/2-inch process pipe and align mounting holes
in adapter with holes in end of process head as required.

4

Secure adapter to process head by hand tightening 7/16-20 hex-
head bolts.
Example - Installing adapter on process head.

Process
Head

Filter Screen

Teflon Gasket

Flange Adapter

7/16 x 20 Bolts

21011

ATTENTION Apply an anti-seize compound on the stainless steel

bolts prior to threading them into the process head.

5

Evenly torque flange adapter bolts to a torque of 27,1 Nm +/- 1,4 Nm
(20 ft lbs +/- 1.0 ft lbs)

38

ST 3000 Release 300 Installation Guide

2/05

Advertising