A.4 setting range values (local zero and span) – Honeywell ST 3000 User Manual

Page 66

Advertising
background image

A.4

Setting Range Values (Local Zero and Span),

Continued

Procedure, continued

Table A-3

Setting Range Values Using Local Zero and Span

Adjustments,

Continued

Step Action

4

Turn ON transmitter power and let it warm up for a few minutes.

Using an accurate pressure source, apply desired zero equivalent

pressure to transmitter.

ATTENTION For differential pressure transmitters, apply pressure

to the high pressure head for positive range values or vent both

heads to atmosphere for zero. If zero is to equal a negative value,

apply the equivalent pressure to the low pressure head. For

example, if zero is to equal –10 inH

2

O, you would apply 10 inH

2

O to

the low pressure head and vent the high pressure head for the zero

adjustment.

5

Check that milliammeter reading is 4 mA.

If reading …

Then…

is less or greater than 4 mA go to Step 6.
is correct

go to Step 7.

ATTENTION If you have the smart meter with local zero and

span adjustment option, you may substitute the smart meter

readings for the milliammeter readings. For example, with zero input

pressure applied assume that the meter reads 4 inH2O instead of 0

inH2O. In this case, the meter reading is greater than 0 (or 4 mA).

6

a. Press and hold ZERO button on local zero and span assembly or

smart meter.

ATTENTION The smart meter readings revert to the default unit of

percent (%) during this operation. If the error code Er0 appears on

the display, you are working with a model STD110 transmitter that

does not support the local zero and span adjustments.

b. Press Decrease button once to complete this function.

ATTENTION The smart meter display goes blank for a 1/2

second and then returns reading 0%.


c. Check that milliammeter reading equals 4 mA and release ZERO

button.

ATTENTION If milliammeter reading doesn’t change, be sure you

are not working with a model STD110 transmitter that ignores local

adjustments. The smart meter readings return to the set engineering

units after you release the ZERO button.

Continued on next page

56

ST 3000 Release 300 Installation Guide

2/05