A.5 configuring smart meter using pushbuttons – Honeywell ST 3000 User Manual

Page 74

Advertising
background image

A.5

Configuring Smart Meter Using Pushbuttons,

Continued

Setting Lower Display
Values,
continued

Table A-7

Setting Lower Display Values for Smart Meter Display

Step Action

Meter

Display

1

You have completed units selection in Table

A-5 and U-L appears on the display. Press

LOWER VALUE button to initiate lower

display limit setting function.

ATTENTION

This procedure is only

applicable for Custom (EUF) engineering unit

selection in a transmitter configured for

LINEAR output conformity.

The lower display value for transmitters

configured for SQUARE ROOT output

conformity is fixed at zero (0.00) and cannot

be changed.

If lower limit display value was previously set,

KNOWN VALUE indicator lights and set value

flashes in display.

%

100

0

ANALOG

UPPER

VALUE

UNITS

LOWER

VALUE

S E T

V A R

SEL.

0 . 0

0

Previously set
value flashes in
display and
indicator lights

KNOWN VALUE

2

Press LOWER VALUE button again within 5

seconds. Otherwise, meter exits limit setting

function.

Display shows magnitude range selection.

%

100

0

ANALOG

UPPER

VALUE

UNITS

LOWER

VALUE

S E T

VAR

SEL.

19 .99

ATTENTION

The magnitude range

selection only applies for setting the display
limits. This selection does not affect the
normal operation of the meter. During normal
operation, the display is automatically ranged
to provide the best precision possible.

Continued on next page

64

ST 3000 Release 300 Installation Guide

2/05