Configuring Smart Meter Using Pushbuttons,

Continued

Setting lower display
values,
continued

Table A-7

Setting Lower Display Values for Smart Meter Display, continued

Step Action

Meter

Display

9

Press Increase button to select the next

available digit value or Decrease button to

select the previous digit value.

Repeat this action until desired value is on

display.

10

Press LOWER VALUE button to lock-in third

digit and activate next active digit.

Readout now displays next active digit which

will be BLANK unless lower value was set to 1

before.

11

Press Increase button to set digit to 1 or

Decrease button to set it to BLANK..

12

Press LOWER VALUE button to lock-in “1”

digit and activate sign segment.

Readout now displays sign segment which

will be BLANK for positive values unless lower

value was set for negative (–) values before.

Third digit value setting.

%

100

0

ANALOG

UPPER

VALUE

UNITS

LOWER

VALUE

S E T

VAR

SEL.

0

0

0 .

0
1
2
3
4
5
6
7
8
9

Press and hold to
scroll forward
through values

Press and hold to
scroll backward
through values

13

Press Increase button to set sign segment

to minus sign for negative values or Decrease

button to set it to BLANK. for positive

values.

14

Press LOWER VALUE button to lock in

current settings as lower display value limit.

ATTENTION

For CUSTOM unit in

transmitter with LINEAR output, you must set

both lower and upper display limits for values

to take effect. If you let either the lower or

upper display limit time out (after 30 seconds),

the meter discards both newly set values and

reverts back to the previously set values.

Sign segment setting.

%

100

0

ANALOG

UPPER

VALUE

UNITS

LOWER

VALUE

S E T

VAR

SEL.

0

0

0 .

Press to set sign
segment as minus
sign (-) for negative
values

Press to set sign
segment as
BLANK for
positive values

• If you have not yet set the upper display limit value, the meter automatically enters the upper display

setting function after it displays previously set value, if applicable. Go to Table A-8.

• If you have already set the upper display limit value, this completes the lower and upper display

limits setting function for Custom engineering units in the transmitter. Meter returns to normal
operation.