A.5

Configuring Smart Meter Using Pushbuttons,

Continued

Setting Upper Display
Values,
continued

Table A-8

Setting Upper Display Value for Smart Meter Display, continued

Step Action

Meter

Display

12

Press UPPER VALUE button to lock-in “1”

digit and activate sign segment.

13

Press Increase button to set sign segment

to minus sign for negative values or Decrease

button to set it to BLANK. for positive

values.

Readout now displays sign segment which

will be BLANK for positive values unless

upper value was set for negative (–) values

before.

%

100

0

ANALOG

UPPER

VALUE

UNITS

LOWER

VALUE

S E T

VAR

SEL.

K

99 90

1

Sign segment
is BLANK for
positive values
and minus sign
for negative
values

14

Press UPPER VALUE button to lock in
current settings as upper display value and
return to previous display. Upper display limit
setting is now complete.

ATTENTION For CUSTOM unit in
transmitter with LINEAR output, you must set
both lower and upper display limits for values
to take effect. If you let either the lower or
upper display limit time out (after 30 seconds),
the meter discards both newly set values and
reverts back to the previously set values.


Display goes blank for a 1/2 second and

returns to display readout equal to 50%

output.
In this example, readout is 9, 990,000

CUSTOM unit for 50% display range of 0 to

19,990,000 CUSTOM for transmitter with

LINEAR output.

%

100

0

ANALOG

UPPER

VALUE

UNITS

LOWER

VALUE

S E T

VAR

SEL.

K

99 90

• If you have not yet set the lower display limit value for CUSTOM unit in a transmitter configured for

LINEAR output mode, the meter automatically enters the lower display setting function after it
displays previously set value, if applicable. Go to Table A-7, Step 3.

• If you have already set the lower display limit value, this completes the lower and upper display limits

setting function for CUSTOM unit in a transmitter configured for LINEAR output mode. Meter returns
to normal operation.

• If you have just set the upper display limit for Flow unit or CUSTOM unit in a transmitter configured

for SQUARE ROOT output mode, this completes the limit setting function. Meter returns to normal
operation.

72

ST 3000 Release 300 Installation Guide

2/05