A.8 typical smart meter indications, Continued, Operation error codes – Honeywell ST 3000 User Manual

Page 91: If error indication is . . . then, it means

Advertising
background image

A.8

Typical Smart Meter Indications,

Continued

Operation error codes

Table A-11 identifies possible meter error codes and what they mean.

Table A-11

Smart Meter Error Codes and Descriptions.

If error indication is . . .

Then, it means

%

100

0

E r

ANALOG

%

0

UPPER

VALUE

UNITS

LOWER

VALUE

S E T

VAR

SEL.

You have tried to set local Zero or Span adjustment in a
Series 100 transmitter that does not support this option.

%

100

0

E r

ANALOG

%

1

UPPER

VALUE

UNITS

LOWER

VALUE

S E T

VAR

SEL.

You have tried to set a pressure type engineering unit for a
transmitter in SQUARE ROOT mode (FLOW) or have tried
to set a flow type engineering unit for a transmitter in
LINEAR mode (pressure). After this error is displayed, the
meter will return to the unit # (EU#) of the Engineering Unit
it was displaying before the set function was invoked. You
may then select another unit or exit in the normal fashion.

%

100

0

E r

ANALOG

%

2

UPPER

VALUE

UNITS

LOWER

VALUE

S E T

VAR

SEL.

You have tried to select a process variable for the
transmitter using the VAR SEL. button. The Variable Select
button is non-functioning on the ST 3000 R300 transmitter.

%

100

0

E r

ANALOG

%

3

UPPER

VALUE

UNITS

LOWER

VALUE

S E T

VAR

SEL.

You have tried to set Lower or Upper display limit for
pressure type engineering units (EU1 to EUC), or Lower

display limit for flow type engineering units (EUD,EUE) or

CUSTOM unit (EUF) in transmitter configured for SQUARE

ROOT output. Or, you have tried to set upper display limit
for flow or Custom unit in transmitter with SQUARE ROOT
output and URV set to zero (0). In SQUARE ROOT mode,
the transmitter’s URV cannot equal zero. The Lower and
Upper display limits only apply for CUSTOM (EUF) unit in

transmitter configured for LINEAR output. The Upper
display limit also applies for FLOW (EUD,EUE) and

CUSTOM (EUF) units with transmitter in SQUARE ROOT

mode , but the Lower display limit is fixed at zero (0) and
cannot be changed.

Continued on next page

2/05

ST 3000 Release 300 Installation Guide

81