B.1

North American Classification of Hazardous
Locations,

Continued

Methods of Protection

The following table summarizes available methods of protection for use
in given locations.

Protection Concept

Designation

Permitted Use

Principle

Explosionproof

XP

Division 1 & 2

Contains explosion and
quenches flame.

Intrinsic Safety

IS

Division 1 & 2

Limit energy of sparks under
normal and fault conditions.

Pressurized

Type X and Y

Division 1

Keeps flammable gas out.

Pressurized

Type Z

Division 2

Keeps flammable gas out.

Nonincendive

NI

Division 2

No arcs, sparks or hot surfaces
under normal conditions

Temperature
Classification

Equipment intended for installation directly within the hazardous
location classification must also be classified for the maximum surface
temperature that can be generated under normal or fault conditions as
referenced to either 40°C (104°F) or the maximum operating ambient of
the equipment (whichever is greater). The maximum surface
temperature must be less than the minimum autoignition temperature of
the hazardous atmosphere present. The temperature shall be indicated in
identification numbers as listed in the following table.

Maximum

Temperature

Degrees C

Degrees F

Identification Number

450 842 T1

300 572 T2

280 536 T2A

260 500 T2B

230 446 T2C

215 419 T2D

200 392 T3

180 356 T3A

165 329 T3B

160 320 T3C

135 275 T4

120 248 T4A

100 212 T5

85 185 T6

Continued on next page

2/05

ST 3000 Release 300 Installation Guide