Honeywell ST 3000 User Manual

Page 96

Advertising
background image

B.1

North American Classification of Hazardous
Locations,

Continued

Apparatus
Parameters

The Intrinsically Safe Apparatus Parameters are defined as follows.

Parameter Description

Vmax

Maximum safe voltage which can be applied to the apparatus
terminals.

Imax

Maximum safe current which can be applied to the apparatus
terminals.

Ci

Unprotected capacitance in the apparatus which can be
considered present at the terminals.

Li

Unprotected inductance in the apparatus which can be
considered present at the terminals.


The Associated Apparatus Parameters are defined as follows.

Parameter Description

Voc

Maximum output voltage which can be delivered to the
hazardous (classified) location. This voltage is the maximum
from a single channel.

Isc

Maximum output current which can be delivered to the
hazardous (classified) location. This current is the maximum
from a single channel.

*Vt

Maximum output voltage which can be delivered to the
hazardous (classified) location. This voltage is the maximum
across any combination of terminals of a multiple channel
configuration.

*It

Maximum output current which can be delivered to the
hazardous (classified) location. This current is the maximum
through any combination of terminals of a multiple channel
configuration.

Ca

Maximum capacitance which can be connected to the
apparatus.

La

Maximum inductance which can be connected to the
apparatus.

*

CSA does not recognize these parameters at this time.

Continued on next page

86

ST 3000 Release 300 Installation Guide

2/05

Advertising