B.1

North American Classification of Hazardous
Locations,

Continued

Table B-1

Factory Mutual (FM) Approval, Continued

Intrinsic Safety

Entity Parameters

(1)

Class I, II, III, Divisions 1 and 2,

Groups A - G

V

Max

≤ 42.4 V

I

Max

= 225 mA

P

Max

= 1.2 W

C

i

= 4.2 nF

L

i

= 0

With no integral indicator, or with
integral Smart Meter, option SM.

L

i

= 150

µH

With Analog Meter, option ME.

(1)

Install in accordance with Honeywell drawing 51204241.

Table B-2

Canadian Standards Association (CSA)

Code Description

2j

Explosion Proof for Class I, Division 1, Groups B, C & D.
Dust-Ignition-Proof for Class II, Division 1, Groups E, F & G;
Class III, Division 1. Conduit seals not required. 42 Vdc max.

Intrinsically Safe for Class I, Groups A, B, C & D; Class II,
Groups E, F & G; Class III, Divisions 1, T4 at 40

°C, T3A at

93

°C maximum ambient. Install per Honeywell drawing

51204242.

Suitable for Class I, II & III, Division 2, Groups A, B, C, D, E, F
& G hazardous locations, T4 at 93

°C. 42 Vdc max.

Environmental: Indoor and outdoor hazardous locations
(Encl 4X).

CSA Certified Barriers

(1)

Class I, II, III, Division 1 and 2,

Groups

28V / 200

A - G

20V / 150

C - G

(1)

Install in accordance with Honeywell drawing 51204242.