SPECIFICATIONS

Compatibility: Full feature set, including scheduling and

password protection requires the latest Spyder firmware

(field upgradeable with Spyder Flash Tool), Spyder Tool

version greater than 5.18, and WEBs-AX Workbench ver-

sion 3.4.57 or greater.

Construction: Two-piece construction, cover and internally

wired subbase. Field wiring, 18 to 24 AWG (0.82 to 0.20

sq. mm), connects to a terminal block in the subbase.

Mounting Options: The LCD wall modules can be mounted

on a standard two by four inch junction box or on a 60 mm

diameter junction box. The modules may be mounted up to

200 ft. (61 m) from the programmable controller. Twisted

pair wiring is recommended for distances longer than 100

ft. (30.5 m).

Dimensions (H/W/D): See Fig. 2 on page 2.
Environmental Ratings:

Operating Temperature: 30°F to 110°F (-1°C to 43°C)

Shipping Temperature: -40°F to 150°F (-40°C to 65.5°C)

Relative Humidity: 5% to 95% non-condensing

Temperature Setpoint Range: Default range is 55°F to 85°F

(10°C to 35°C); configurable for other ranges.

Temperature Sensor Accuracy: ±0.36°F at 77°F (±0.2°C at

25°C)

Humidity Sensor Accuracy (TR71-H/TR75-H only): ±5%

RH from 20% to 80% RH

Power: 18 Vdc power is supplied to the wall module from the

2-wire S-BUS connection to the programmable

controller.

Accessories: 50007298-001 (pack of 12) medium, cover

plate; 6-7/8 x 5 in. (175 x 127 mm).

Approvals: CE; UL94-HB plastic enclosure; FCC Part 15,

Class B

Terminal Wiring Location

Fig. 1 illustrates the location of the terminal block and other

features on the TR70 Series wall modules.

Fig. 1. LCD wall module components (rear view).

NOTE: 18 Vdc power for the LCD wall modules is sup-

plied from the programmable controller.

Module Dimensions

Fig. 2. Wall module dimensions in inches (mm).

Communications

The wall modules use a sensor bus (S-BUS) for

communications with the programmable controller.

For network communication, the building’s LON or BACnet®

network wires connect to the two terminals (NET-1 and NET-

2). See Fig. 1. A network bus port is accessible at the bottom

of the wall module by removing the jack plug.

The network bus and S-BUS terminals (see Fig. 1) are

insensitive to polarity, minimizing installation errors due to

mis-wiring. The recommended wire size for the network bus

M27349

SLOTS FOR SUBBASE

LOCKING TABS (X4)

0

1 2 3

4

9

8 7 6

5

WALL MODULE BUS

ADDRESS DIAL

(DEFAULT SETTING = 1)

S-BUS PROGRAMMABLE

CONTROLLER CONNECTION

NETWORK BUS

CONNECTION

EACH OF THE TWO WIRE CONNECTIONS FOR THE S-BUS AND NETWORK

BUS TERMINALS ARE POLARITY INSENSITIVE.

1 2 3 4

1

1

50028668-XXX

4

3

2

1

S-BUS

S-BUS

NET-2

(optional)

NET-1

(optional)

TR70-H

YY WK

HONEYWELL

PATENT PENDING

GOLDEN VALLEY,MN

ASSEMBLED IN MEXICO

3 5/16 (84)

4 5/8

(117)

15/16

(24)

M27347

Advertising
This manual is related to the following products: