Communications, Before installation, Installation – Honeywell ZIO TR75 User Manual

Page 2: Caution

Advertising
background image

ZIO

®

/ZIO PLUS LCD WALL MODULES

62-0271—07

2

Communications

The wall modules use a sensor bus (S-BUS) for

communications with the programmable controller. Wire the

two S-BUS terminals according to these installation

instructions.

The wall modules have a network bus port for L

ON

M

ARK

® or

BACnet® communications. If network communication is

needed, connect the building LON network wires to the two

terminals (NET-1 and NET-2), according to these installation

instructions. A network bus port is accessible at the bottom of

the wall module by removing the jack plug. See Fig. 1.

The network bus and S-BUS terminals (see Fig. 6 on page 4)

are insensitive to polarity, minimizing installation errors due to

mis-wiring.

BEFORE INSTALLATION

Fig. 1. LCD Wall Module features.

CAUTION

Erratic System Operation Hazard.

Failure to follow proper wiring practices can

introduce disruptive electrical interference (noise).

Keep wiring at least one foot away from large inductive

loads such as motors line starters, lighting ballasts,

and large power distribution panels.

Shielded cable is required in installations where these

guidelines cannot be met.

Ground the shield only to the grounded controller

case.

IMPORTANT

All wiring must comply with local electrical codes and

ordinances or as specified on installation wiring dia-

grams.

— Wall module wiring can be sized from 18 to 24 AWG (0.82

to 0.20 sq. mm), depending on the application. For

multiple Zios on the same S-BUS, 24 AWG wire is

recommended.

— For S-BUS wiring, the Zio may be mounted up to 200 ft.

(61 m) from the programmable controller. If multiple Zios

are installed, the total distance from the controller to the

last Zio should not exceed 200 ft.

— Twisted pair wire is recommended for wire runs longer than

100 ft. (30.5 m).

— All wiring is polarity insensitive.

— The cover for the wall module is packed separately from

the subbase for ease of installation.

INSTALLATION

Mount the wall module on an inside wall approximately 54 in.

(1372 mm) from the floor (or in the specified location), to allow

exposure to the average zone temperature. Do not mount the

wall module on an outside wall, on a wall containing water

pipes, or near air ducts. Avoid locations that are exposed to

discharge air from registers or radiation from appliances,

lights, or the sun.

The wall module can be mounted on a wall, on a standard

utility conduit box using No. 6 (3.5 mm) screws or on a 60 mm

wall outlet box (see Fig. 3). When mounting directly on a wall,

use the type of screws appropriate for the wall material.

Fig. 2. Subbase mounting holes and locking tabs.

LCD PANEL

M27344

SOFTKEYS (3)

UP/DOWN

ARROW KEYS

NETWORK BUS PORT (ON BOTTOM OF CASE)

2-3/8 (60)

2-3/8

(60)

3-1/4

(83)

M27345

LOCKING

TABS (4)

2-3/8 (60)

3-3/8 (95)

4-1/8

(105)