I introduction, Ii specifications and certifications, Specifications – Hubbell Fire Pump Controller LX-1500 User Manual

Page 3

Advertising
background image

Limited Service Fire Pump Controller

Page 3 of 12

I Introduction

The Hubbell Limited Service Fire Pump Controller provides automatic and manual control of
small electric motor driven fire pumps and booster pumps of 30 horsepower or less.

All Controller components are inside the cabinet with indicating lights and switch handles
located next to the door. A pressure switch initiates automatic starting of the pump motor. The
Controller monitors the power phases and voltage. The CIRCUIT BREAKER
DISCONNECTING MEANS handle has a door interlock feature to prevent opening the door
when the switch is closed. The Controller also has an EMERGENCY MANUAL CONTROL
handle to start the fire pump manually.

Control
Panel

Incoming
Phase
Line

Surge

Suppressor

To
Fire Pump Motor

L1 M1 T1

PLM

Pressure
Switch

EMERGENCY
MANUAL
CONTROL

Control
Transformer

CIRCUIT

BREAKER

DISCONNECTING

MEANS

Figure I-1 Block diagram of LX-1500 showing one phase

II Specifications and Certifications

Specifications

Voltage

208, 240, 380, 480C

Phase Loss/Reversal Module

A-B-C phase rotation

200 Series
300 Series
400 Series

208–240 VAC, 60 Hz, 3 phase
380–415 VAC, 50 Hz, 3 phase
440–480 VAC, 60 Hz, 3 phase

Maximum Voltage

10% of highest nominal voltage

Maximum Frequency Shift

0.1 Hz

Phase Loss

18% of low voltage in one phase

Advertising