Operation and checkout – Honeywell VBN2 User Manual

Page 3

Advertising
background image

VBN2, VBN3 CONTROL BALL VALVE/ACTUATOR ASSEMBLIES

3

62-0197—04

Fig. 6.

Valve assembly exploded view.

OPERATION AND CHECKOUT

Once both the mechanical and electrical installations are

complete:

1. Cycle the actuator to verify that the direction of rota-

tion suits the control sequence.

2. If the rotation direction is incorrect:

a. For 2-position control actuators: Remount actu-

ator on the bracket.

b. For floating control actuators: Reverse two con-

trol signal wires (CW/CCW).

c. For analog control actuators either:

(1) Reposition reverse/direct acting switch, or
(2) Remount actuator on the bracket.

3. If the control scheme requires fail-safe operation,

ensure that, upon removal of power, the valve
rotates to the desired position.

4. Spring return actuators are factory-configured for

A-port normally-closed fail-safe operation. To
change this to normally-open, remove and reinstall
the actuator in the opposite orientation as follows:

(a) Loosen the shaft coupling bolt using a 10

mm wrench.

(b) Loosen all other mounting bolts connect-

ing the actuator to the mounting bracket,
and set aside.

(c) Remove the actuator from the valve

shaft.

(d) Move the actuator shaft coupling to the

opposite side of the actuator, as displayed
in Figure 7.

Fig. 7. SCSA Mounting

For detailed actuator information, see Honeywell forms:
— 63-2209 ML6161,ML7161 Product Data Sheet.
— 63-2607 S05,S10,S20 Series Actuator Product Data

Sheet.

M29526

VALVE BODY

VALVE STEM

COUPLER

WING NUT

MOUNTING

PLATE

ANTI-ROTATION

BRACKET

BOLT

STEM ASSEMBLY COVER

SCREWS (2)

HANDLE (REMOVABLE) FOR

MANUALLY ROTATING SHAFT

STEM ASSEMBLY

SCREWS (2)

STEM RETAINER PLATE

BOLT

ANTI-ROTATION

BRACKET

1

2

INCLUDED IN REPLACEMENT KIT (PART NO. 5112-11).

THIS PART USED WITH NON-SPRING RETURN ACTUATORS.

1

2

1

1

1

1

1

1

1

1

1

M27714

Advertising
This manual is related to the following products: