INSTALLATION INSTRUCTIONS

® U.S. Registered Trademark
Copyright © 1996 Honeywell Inc. • • All Rights Reserved

Q7300A,C,D,G Series 2000

Commercial Thermostat Subbases

APPLICATION

The Q7300 Thermostat Subbases are used with T7300
Thermostats to provide electronic control of commercial

24 Vac single or multistage heat pump or conventional
heating and cooling systems. Select models have termi-
nals for LEDs and remote temperature sensors. Refer to
Table 1. All Q7300 Thermostat Subbases require a
common wire to the supply power.

Table 1. Description of Q7300 Subbases.

a

Depends on model.

RECYCLING NOTICE

If this control is replacing a control that contains
mercury in a sealed tube, do n

ot

place your old

control in the trash

Contact your local waste management authority for
instructions regarding recycling and the proper
disposal of the old thermostat.

INSTALLATION

When Installing this Product…

1. Read these instructions carefully. Failure to follow

the instructions can damage the product or cause a
hazardous condition.

2. Check the ratings given in the instructions and on

the product to make sure the product is suitable for
your application.

3. Installer must be a trained, experienced service

technician.

4. After completing installation, use these instructions

to check out the product operation.

Location

Subbase without Remote-Mounted
Temperature Sensor

Install the thermostat about 5 ft (1.5m) above the floor in
an area with good air circulation at average temperature.
See Fig. 1.

Do not install the thermostat where it can be affected by:

drafts, or dead spots behind doors and in corners.

hot or cold air from ducts.

radiant heat from sun or appliances.

concealed pipes and chimneys.

unheated (uncooled) areas such as an outside wall
behind the thermostat.

Subbase with Remote-Mounted
Temperature Sensor(s)

If only the remote-mounted temperature sensor(s) is used
to sense and control room temperature, then install the
thermostat in an area that is accessible for setting and
adjusting the temperature and settings.

If both the subbase and remote-mounted temperature
sensor(s) are used to sense and control room tempera-
ture, then install the subbase about 5 ft above the floor in
an area with good air circulation.

Maximum Stages

a

Model

Applications

Thermostat Required

Heat

Cool

Hookup Drawing

Q7300A

Conventional

T7300D, F

2

2

9-12

Q7300C

Heat Pump

T7300E, F

3

2

13-15

Q7300D

Heat Pump

T7300E, F

3

2

16

Q7300G

Conventional

T7300D, F

3

3

17