Ml6194 and ml6294 wiring for common transformer, Operation – Honeywell ML6194 User Manual

Page 7

Advertising
background image

ML6194, ML6294 NON-SPRING RETURN DIRECT COUPLED ACTUATORS

7

63-2511—1

Fig. 9. ML6294D,F typical wiring diagram.

The ML6194/ML6294 has a plastic housing with two tapped

holes for 1/2 in. (13 mm) conduit fittings.

ML6194 and ML6294 Models with Factory-

mounted Auxiliary Switches (see Fig. 10)

ML6194C,F and ML6294C,F models have two nonadjustable

low voltage rated spdt auxiliary switches that are factory set to

make common to normally open at 12° and 82° rotation from

closed (counterclockwise). See Fig. 10.

Fig. 10. ML6194C,F and ML6294 Actuator wiring for

auxiliary switches.

ML6194 and ML6294 Wiring for Common

Transformer

Fig. 11 through 13 show typical wiring for ML6194 and

ML6294 Non-Spring Return DCA using a common

transformer.

Fig. 11. Common transformer with two controller outputs

and two ML6194A,C or ML6294A,C Actuators.

Fig. 12. Common transformer with two controller outputs

and two ML6194D,F or ML6294D,F Actuators.

OPERATION

The ML6194 and ML6294 Non-Spring Return DCA are

designed to be used in ventilating and air conditioning

installations to operate dampers, ventilation flaps, and louvers

requiring up to 300 lb-in. torque.

The ML6194 and ML6294 Non-Spring Return DCA are

operated by an spdt floating controller. When using an spdt

floating controller, actuator is driven toward fully open

(clockwise) position when controller makes B contact and

toward fully closed (counterclockwise) position when

controller makes W contact. It stops when neither contact is

made.

L1

(HOT)

L2

1

1

2

2

3

3

MOTOR

TIME OUT

24 VAC

B

BLUE

W

YELLOW

T2

RED

T1

BLACK

ML6294

M11280A

POWER SUPPLY. PROVIDE DISCONNECT MEANS AND

OVERLOAD PROTECTION AS REQUIRED.

TIME-OUT FUNCTION AVAILABLE WITH ML6294D,F MODELS.

500 OHM POTENTIOMETER.

ORANGE (OPEN)

TAN

GREEN (CLOSED)

CONTROLLER

12

82

M7877A

COMMON

COMMON

NO

NO

NC

NC

WHITE/RED

WHITE/BLUE
WHITE/YELLOW
BLACK/RED

BLACK/BLUE

BLACK/YELLOW

INTERNAL

AUXILIARY

SWITCH

3A, 24 VAC

SWITCHES SHOWN AT ACTUATOR (CCW)

CLOSED POSITION.

L1

(HOT)

L2

1

1

BLACK

BLACK

ML6194A,C

ML6294A,C

ML6194A,C

ML6294A,C

M11277A

POWER SUPPLY. PROVIDE DISCONNECT MEANS

AND OVERLOAD PROTECTION AS REQUIRED.

CONTROLLER

CONTROLLER

BLUE

YELLOW

BLUE

YELLOW

L1

(HOT)

L2

1

1

RED
BLACK

RED

BLACK

ML6194D,F

ML6294D,F

ML6194D,F

ML6294D,F

M11278A

POWER SUPPLY. PROVIDE DISCONNECT MEANS

AND OVERLOAD PROTECTION AS REQUIRED.

CONTROLLER

CONTROLLER

BLUE

YELLOW

BLUE

YELLOW

Advertising
This manual is related to the following products: