SOLID CORE AND SPLIT CORE 4-20 MA OUTPUT CURRENT SENSORS

3

62-0245—01

aperture (hole) size of the current sensor is
3/4 in. (19 mm) and will accept a maximum cable
diameter of 350 MCM (17.3 mm).

Fig. 6. Wiring example

OPERATING SPECIFICATIONS

Max Sensing Current Voltage: 600 Vac

M23934

BUILDING AUTOMATION

SYSTEM

COMMON

+ 4-20 MA SIGNAL INPUT

GND (SHIELD)

+

+12-30 VDC

DC POWER SUPPLY

+

Table 1. Specifications by Product Number

Product Number

Core
Type

Output

Range

Jumper

a

Max. Current

Continuous

Max. Current

for 6 secs.

CTS-20-005-AVG-001

Solid

4-20 mA Average

0-5 Amps Fixed None

100 Amps

125 Amps

CTS-20-050-AVG-001

Solid

4-20 mA Average

0-10 Amps
0-20 Amps
0-50 Amps

Low
Middle
High

100 Amps
150 Amps
200 Amps

125 Amps
225 Amps
300 Amps

CTS-20-250-AVG-001

Solid

4-20 mA Average

0-100 Amps
0-200 Amps
0-250 Amps

Low
Middle
High

200 Amps
360 Amps
400 Amps

250 Amps
450 Amps
500 Amps

CTS-20-005-VFD-001

b

Solid

4-20 mA True RMS

0-5 Amps Fixed None

60 Amps

100 Amps

CTS-20-050-VFD-001

b

Solid

4-20 mA True RMS

0-10 Amps
0-20 Amps
0-50 Amps

Low
Middle
High

60 Amps
100 Amps
160 Amps

80 Amps
200 Amps
300 Amps

CTS-20-250-VFD-001

b

Solid

4-20 mA True RMS

0-100 Amps
0-200 Amps
0-250 Amps

Low
Middle
High

160 Amps
320 Amps
400 Amps

200 Amps
400 Amps
500 Amps

CTP-20-005-AVG-001

Split

4-20 mA Average

0-5 Amps Fixed None

100 Amps

125 Amps

CTP-20-050-AVG-001

Split

4-20 mA Average

0-10 Amps
0-20 Amps
0-50 Amps

Low
Middle
High

100 Amps
150 Amps
200 Amps

125 Amps
225 Amps
300 Amps

CTP-20-200-AVG-001

Split

4-20 mA Average

0-100 Amps
0-150 Amps
0-200 Amps

Low
Middle
High

135 Amps
180 Amps
250 Amps

200 Amps
300 Amps
400 Amps

CTP-20-005-VFD-001

b

Split

4-20 mA True RMS

0-5 Amps Fixed None

60 Amps

100 Amps

CTP-20-050-VFD-001

b

Split

4-20 mA True RMS

0-10 Amps
0-20 Amps
0-50 Amps

Low
Middle
High

60 Amps
100 Amps
160 Amps

80 Amps
200 Amps
300 Amps

CTP-20-200-VFD-001

b

Split

4-20 mA True RMS

0-100 Amps
0-150 Amps
0-200 Amps

Low
Middle
High

135 Amps
180 Amps
250 Amps

200 Amps
300 Amps
400 Amps

a

All current sensors are shipped from the factory with the jumper set in the high range.

b

All VFD models have True RMS outputs and should be used with Variable Frequency Drives. Not CE compliant at
this time.