Technical data

Honeywell

Honeywell

Honeywell

Honeywell

4

4.3

Technical data

Input voltage U

in

380 - 500V, -15%...+10% 3~
208…240V, -15%...+10% 3~
208…240V, -15%...+10% 1~

Input frequency

45…66 Hz

Mains
connection

Connection to mains

Once per minute or less (normal case)

Output voltage

0—U

in

Continuous output
current

I

L

: Ambient peak temperature max. +45°C (with 24h

average ambient +40°C),*

overload 1.1 x IL (1min/10min)
I

H

: Ambient temperature max. +50ºC,

overload 1.5 x IH (1min/10min)

Starting torque

150% (Low overload); 200% (High overload)

Starting current

2 x IH 2 seconds every 20 seconds, if output frequency
<30Hz
and temperature of heatsink <+60ºC

Output frequency

0…320 Hz

Motor
connection

Frequency resolution

0,01 Hz

Control method

Frequency Control U/f
Open Loop Sensorless Vector Control

Switching frequency
(See parameter 2.6.8)

1...16 kHz; Factory default 6 kHz

Frequency reference
Analogue input
Keypad reference


Resolution 0.1% (10bit), accuracy ±1%
Resolution 0.01 Hz

Field weakening point

30…320 Hz

Acceleration time

0.1…3000 sec

Deceleration time

0.1…3000 sec

Control
characteristics

Braking torque

DC-brake: 30%*TN (without brake option)

Ambient operating
temperature

–10°C (no frost)…+45°C: I

L

(ambient temperature derating 1,5%/Cº)

–10°C (no frost)…+50°C: I

H

Storage temperature

–40°C…+70°C

Relative humidity

0…95% RH, non-condensing, non-corrosive,
no dripping water

Air quality:
- chemical vapours
- mechanical particles


IEC 721-3-3, unit in operation, class 3C2
IEC 721-3-3, unit in operation, class 3S2

Altitude

100% load capacity (no derating) up to 1000m
1-% derating for each 100m above 1000m; max. 3000m

Vibration:
EN50178/EN60068-2-6

5...150 Hz
Displacement amplitude 1(peak) mm at 5...15.8 Hz
Max acceleration amplitude 1 G at 15.8...150 Hz

Shock
EN50178, IEC 68-2-27

UPS Drop Test (for applicable UPS weights)
Storage and shipping: max 15 G, 11 ms (in package)

Ambient
conditions

Enclosure class

IP20; MF2 and MF3. IP21/IP54; MF4 – MF6

Technical data (continues on next page)

* In NXL Compact the maximum ambient operation temperature is +40°C. (+45°C only applies to NXL HVAC)