5.2

Cooling

Forced air flow cooling is used for NXL HVAC and NXL Compact size MF3.

Enough free space shall be left above and below the frequency converter to ensure sufficient air
circulation and cooling. You will find the required dimensions for free space in the table below.


Type

Dimensions [mm]

A

B

C

D

NXL 0002-0006 2

10

10

100

50

NXL 0001-0005 5

10

10

100

50

HVAC 03-12

20

20

100

50

HVAC 16-31

20

20

120

60

HVAC 38-61

30

20

160

80

Table 5-4. Mounting space dimensions

Figure 5-6. Installation space

Type

Cooling air required [m

3

/h)

HVAC 03—12

70

HVAC 16—31

190

HVAC 38—61

425

Table 5-5. Required cooling air

A

= clearance around the freq. converter (see also B)

B

= distance from one frequency converter to another or

distance to cabinet wall

C

= free space above the frequency converter

D

= free space underneath the frequency converter