Cabling and connections

Honeywell

Honeywell

Honeywell

Honeywell

6


6.1.1.1

Cable and fuse sizes


Terminal cable size (min/max)

Frame

Type

I

L

[A]

Fuse

[A]

Mains

cable

Cu [mm

2

]

Main terminal

[mm

2

]

Earth

terminal

[mm

2

]

Control

terminal

[mm

2

]

Relay

terminal

[mm

2

]

MF2

NXL0002

2

10

2*1.5+1.5

0.5—2.5

0.5—2.5

0.5—1.5

0.5—2.5

MF3

NXL0003—0006

3-6

16

2*2.5+2.5

0.5—2.5

0.5—2.5

0.5—1.5

0.5—2.5

Table 6-2. Cable and fuse sizes for NXL Compact, 208 - 240V

Terminal cable size (min/max)

Frame

Type

I

L

[A]

Fuse

[A]

Mains

cable

Cu [mm

2

]

Main terminal

[mm

2

]

Earth

terminal

[mm

2

]

Control

terminal

[mm

2

]

Relay

terminal

[mm

2

]

MF2

NXL0001—0002

1-2

10

3*1.5+1.5

0.5—2.5

0.5—2.5

0.5—1.5

0.5—2.5

MF3

NXL0003—0005

1-5

10

3*1.5+1.5

0.5—2.5

0.5—2.5

0.5—1.5

0.5—2.5

MF4

HVAC03—09

7—9

10

3*1.5+1.5

1—4

1—2.5

0.5—1.5

0.5—2.5

MF4

HVAC12

12

16

3*2.5+2.5

1—4

1—2.5

0.5—1.5

0.5—2.5

MF5

HVAC16

16

20

3*4+4

1—10

1—10

0.5—1.5

0.5—2.5

MF5

HVAC23

22

25

3*6+6

1—10

1—10

0.5—1.5

0.5—2.5

MF5

HVAC31

31

35

3*10+10

1—10

1—10

0.5—1.5

0.5—2.5

MF6

HVAC38—45

38-

45

50

3*10+10

2.5—50 Cu

6—50 Al

6—35

0.5—1.5

0.5—2.5

MF6

HVAC61

61

63

3*16+16

2.5—50 Cu

6—50 Al

6—35

0.5—1.5

0.5—2.5

Table 6-3. Cable and fuse sizes for NXL, 380 – 500V


Note! This cable recommendation is based on standard EN 60204-1 and PVC isolated cable where there
is either one cable on a shelf in temperature of + 40°C or four cables on a shelf in temperature of + 30°C.