Cabling and connections 45(96), 4 control i/o – Honeywell NXL User Manual

Page 45

Advertising
background image

Cabling and connections

45(96)

6


6.2.4 Control I/O


Terminal

Signal

Description

1

+10V

ref

Reference output

Voltage for potentiometer, etc.

2

AI1+

Analogue input, voltage range
0—10V DC.

Voltage input frequency reference

3

AI1-

I/O Ground

Ground for reference and controls

4

AI2+

5

AI2-

/GND

Analogue input, current range
0—20mA

Current input frequency reference

6

+24V

Control voltage output

Voltage for switches, etc. max 0.1 A

7 GND

I/O ground

Ground for reference and controls

8

DIN1

Start forward (programmable)

Contact closed = start forward

9

DIN2

Start reverse (programmable)

Contact closed = start reverse

10

DIN3

Preset speed selection 1
(programmable)

Contact closed = Preset speed 1

11

GND

I/O ground

Ground for reference and controls

18

AO1+

19

AO1-

Output frequency
Analogue output

Programmable
Range 0—20 mA/R

L

, max. 500Ω

A

RS 485

Serial bus

Differential receiver/transmitter

B

RS 485

Serial bus

Differential receiver/transmitter

30

+24V

24V aux. input voltage

Control power supply backup

21

RO1

22

RO1

23

RO1

Relay output 1

FAULT

Programmable

Table 6-7. Default I/O configuration.

Terminal

Signal

Description

12

+24V

+24 V DC

Control voltage output; voltage for
switches etc.

13

GND

I/O ground

Ground for reference and controls

14 Exp DIN1 Preset speed selection 2

(programmable)

Contact closed = Preset speed 2

15 Exp DIN2 Fault Reset

(programmable)

Contact closed = Fault reset

16 Exp DIN3 Disable PID (PID control

selection)
(Programmable)

Contact closed = Disable PID

25 Exp RO1
26 Exp RO1

Expander Relay output 1 (NO)
RUN

Programmable

28

TI+

29

TI-

Motor Thermistor input

Active = Fault, stop according to defined
method

Table 6-8. Additional inputs in NXL HVAC (available as option for NXL Compact)

Terminal

Signal

Description

1

+10V

ref

Reference output

Voltage for potentiometer, etc.

2

AI1+

or

DIN 4

Analogue input, voltage range
0—10V DC

Voltage input frequency reference (MF2-3)
Voltage/current input frequency reference
(MF4-MF6)
Can be programmed as DIN4

3

AI1-

I/O Ground

Ground for reference and controls

4

AI2+

5

AI2-

/GND

Analogue input, voltage range
0—10V DC or current range
0—20mA

Voltage or current input frequency
reference

6

+ 24 V

Control voltage output

7 GND

I/O ground

Ground for reference and controls

Table 6-9. AI1 configuration, when programmed as DIN4

Reference
Potentiometer 1-10

kΩ

mA