Control Keypad

Honeywell

Honeywell

Honeywell

Honeywell

7

=

Start button.

Pressing this button starts the motor if the keypad is the active control
place. See Chapter 7.4.3.1.


=

Stop button.

Pressing this button stops the motor (unless disabled by parameter P3.4).

Stop button serves also for activating the Start-up Wizard (see below)


7.3

Start-up wizard

NXL has a built-in start-up wizard, which speeds up the programming of the drive. The wizard helps
you choose between four different operating modes, Standard, Fan, Pump and High Performance.
Each mode has automatic parameter settings optimised for the mode in question. The programming
wizard is started by pressing the Stop button for 5 seconds, when the drive is in stop mode. See the
figure below for the procedure:

Figure 7-3. NXL Start-up wizard


Note! See the Application manuals for detailed parameter descriptions.

start

stop

START-UP WIZARD

ENTER

reset

Push 5 seconds

to activate (in

stop mode)

=Push the button

Tune

n(rpm)

rpm

Tune

I(A)

A

0

Hz

50

Hz

3
s

3
s

I *1,5

400

V

*

50

Hz

0=

Ramp

0=

Coasting

0=

Not

used

0=

Ai1

0-10V

0=

Not

used

20

Hz

50

Hz

20

s

20

s

I *1,1

400

50

Hz

0=

Ramp

0=

Coasting

0=

Not

used

0=

Ai1

0-10V

0=

Not

used

20

Hz

50

Hz

5
s

5
s

I *1,1

400

50

Hz

0=

Ramp

1=

Ramp

0=

Not

used

0=

Ai1

0-10V

0=

Not

used

0

Hz

50

Hz

1
s

1

s

I *1,8

400

50

Hz

0=

Ramp

0=

Coasting

1=

automatic

torque

boost

0=

Ai1

0-10V

0=

Not

used

Standard

Fan

Pump

High

performance

Accept

Accept

H

H

L

L

M

ENTER

reset

Select the

mode. See

table below!

Accept

1

2

4

6

START

MODE

rpm

n

I

n

(A)

DONE

3

5

7

+

-

+

-

+

-

+

-

+

-

+

-

ENTER

reset

ENTER

reset

ENTER

reset

I/O

I/O

I/O

I/O

V

*

V

*

V

*

*In drives of 208V...230V

this value is 230V

NOTE! Startup Wizard resets all

other parameters to factory

defaults!

Honeywell

Honeywell

Honeywell

Honeywell

Honeywell

**

**

** In NXL HVAC the default start function for Fan or Pump
mode is 2 = Conditional Flying Start which is
recommended start function with Trip Free Output
Switching function enabled as standard.

**